P9 ASD Installation and Operation Manual
Slip Frequency Gain
Program
Motor
Vector Motor Model
This parameter provides a degree of slip compensation for a given load. A
higher setting here decreases the slip allowed for a given load/ASD output ratio.
Direct Access Number — F401
Parameter Type —
Numerical
Factory Default —
70
Changeable During Run —
Yes
Minimum — 0
Maximum — 150
Units — %
Autotuning 2
Program
Motor
Vector Motor Model
This parameter introduces a thermal element into the autotuning equation and is
used to automatically adjust the
Autotune
parameter values as a function of
increases in the temperature of the motor.
Settings:
0 — Off
1 — Self-Cooled Motor Tuning
2 — Forced Air Cooled Motor Tuning
Direct Access Number — F402
Parameter Type —
Selection List
Factory Default —
Off
Changeable During Run —
No
(Virtual Linear Pump) Transducer Minimum Reading
Program
Virtual Linear Pump
Virtual Linear Pump Settings
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the minimum level of the transducer range for
Virtual Linear
Pump
operation.
Direct Access Number — F403
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — -32767
Maximum — 32767