P9 ASD Installation and Operation Manual
OP2
Over-Voltage During
Deceleration
• Deceleration time is too short.
• DBR value is too high.
• DBR is required (DBR setup is required).
• Stall protection is disabled.
• 3-phase input voltage is out of specification.
• Input reactance is required.
OP3
Over-Voltage During
Run
• Load fluctuations.
• 3-Phase input voltage is out of specification.
• DBR is required (DBR setup is required).
OT
Over-Torque
• A torque requirement by the load in excess of the setting of
for
a time longer than the setting of
.
• The ASD is improperly matched to the application.
• The load is obstructed.
SEAL
Sealing Water Error
• Inadequate pump seal water.
• Loss of pump seal water.
SOUT
Step-Out
(for PM Motor Only)
• Motor shaft is locked.
• Output phase is open.
• Operating a reciprocating load.
UP1
Main Power
Under-Voltage
• Input 3-phase voltage is too low.
• Momentary power failure longer than the time setting of
UP2
Control Power
Under-Voltage
• This fault is caused by an under-voltage condition at the 5, 15, or the 24 VDC
supply.
• 3-phase input voltage is low.
Note:
The event that caused the trip(s) must be corrected or must decrease to less than the threshold value
required to cause the trip to allow for a Reset to be recognized. In the event of multiple active trips,
the trip displayed will remain until all faults are corrected and cleared.
Table 15. P9 ASD Fault Listing. (Continued)
LED Screen
LCD Screen
Possible Causes/Troubleshooting