P9 ASD Installation and Operation Manual
73
Virtual Linear Pump Setup
Toshiba International Corporation’s
Virtual Linear Pump
algorithm allows for direct and precise
control of pressure, flow rate, or level. This is achieved without the concerns, instabilities, or
complexities that are traditionally associated with pumping system control.
This section provides useful setup and operational information for the
Virtual Linear Pump
system.
The system is initially configured using the (Program
Virtual Linear Pump
)
Virtual Linear
Pump Setup Wizard
. Once the Wizard is started, it must be completed for normal
Virtual Linear
Pump
operations to function.
However, the parameters addressed while using the Wizard or the
Virtual Linear Pump Settings
menu
selection are also accessible via their associated direct access numbers for specific adjustments when
required.
If not using the Wizard to configure the settings of the
Virtual Linear Pump
algorithm, parameter
must first be set to
255: Virtual Linear Pump
to accept the new or changed
Virtual Linear
Pump
parameter settings. Upon completion of the parameter changes, set parameter
to
1
or
2
to
use the changed (new) settings for normal
Virtual Linear Pump
operations (Zero may be selected at
to save the changes to be used later).
The setup procedure and the Wizard setup screens are shown below.
Figure 29. Input the Electrical Specifications of the Motor.
Figure 30. Input the Specifications of the Transducer.
1. Enter the
FLA
from the
nameplate of the motor.
2. Select
Pressure
or
Level
.
3. Select the command source:
EOI
or
V/I
analog input.
4. Set the
Low Frequency
Limit
. 15 Hz fits most
applications.
5. Click
Next
to continue.
6. Set the unit of measure for
the transducer: pressure,
flow rate, or level (i.e., PSI,
GPM, Inches of Water
Column, Feet of Water
Column, or Cubic Feet per
Minute).
7. Select the transducer output
range and signal type:
Current
or
Voltage
.
8. Set the full-scale reading of
the transducer.
9. Click
Next
to continue.