P9 ASD Installation and Operation Manual
141
Drooping Insensitive Torque
Program
Feedback
Drooping Control
This parameter defines a torque range in which the
Drooping
Control
settings
will be ignored and the programmed torque settings will be followed.
Direct Access Number — F323
Parameter Type —
Numerical
Factory Default —
10.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.0
Units — %
Drooping Output Filter
Program
Feedback
Drooping Control
This parameter is used to set the rate of output change allowed when operating
in the
Drooping Control
mode.
Jerky operation may be reduced by increasing this setting.
Direct Access Number — F324
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 200.0
Units — Radians/Second
Braking Mode Selection
Program
Torque
Torque Control
This parameter is primarily used with lifting systems to allow for enough torque
to be produced after receiving a
Run
command before releasing the brake.
Without this feature, the load would drop for a period once the brake was
released.
This parameter enables this function by setting the system operating mode.
Settings:
0 — Disabled
1 — Forward Direction
2 — Reverse Direction
3 — Same Direction
Direct Access Number — F341
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Torque Bias Input Selection
Program
Torque
Torque Control
Once enabled at
, this parameter sets the source of the input signal that will
set the torque level used to provide the
Braking Mode Selection
function of
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — EOI (Keypad)
5 — RS485 2-Wire
6 — RS485 4-Wire
7 — Communication Option Board
8 — RX2 Option (AI1)
Direct Access Number — F342
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes