P9 ASD Installation and Operation Manual
265
OC3P
Overheat During Run
• Cooling fan is inoperative.
• Ventilation openings are obstructed.
• Internal thermistor is disconnected.
• Improper V/f setting.
• ASD or the motor is improperly matched to the application.
OCA1 or OCL
U-Phase Over-Current
• Low impedance at the U lead of the ASD output.
OCA2 or OCL
V-Phase Over-Current
• Low impedance at the V lead of the ASD output.
OCA3 or OCL
W-Phase Over-Current
• Low impedance at the W lead of the ASD output.
OCR
Dynamic Braking
Resistor Over-Current
• ASD inability to discharge the bus voltage during regeneration.
• No dynamic braking resistor (DBR) installed.
• Deceleration time is too short.
• Improper DBR setup information.
• Defective IGBT7 (or IGBT7 ckt.).
• 3-phase input voltage is above specification.
OH
Overheat
• Cooling fan inoperative.
• Ventilation openings are obstructed.
• Internal thermistor is disconnected.
OH2
External Overheat
• Excessive-heat signature received at the
TB3
–
TH1
(+) and
TH1
(-)
for setup information.
OL1
ASD Overload
• Acceleration time is too short.
• DC Injection current is too high.
• Improper V/f setting.
• Motor is running during restart.
• ASD or the motor is improperly matched to the application.
OL2
Motor Overload
• Improper V/f setting.
• Motor is locked.
• Continuous operation at low speed.
• Load requirement exceeds ability of the motor.
• Startup frequency setting adjustment required.
OLR
Dynamic Braking
Resistor Overload
• Deceleration time is too short.
• DBR setting adjustment is required.
• Over-Voltage Stall setting adjustment is required.
OP1
Over-Voltage During
Acceleration
• Motor is running during restart.
Note:
The event that caused the trip(s) must be corrected or must decrease to less than the threshold value
required to cause the trip to allow for a Reset to be recognized. In the event of multiple active trips,
the trip displayed will remain until all faults are corrected and cleared.
Table 15. P9 ASD Fault Listing. (Continued)