P9 ASD Installation and Operation Manual
179
Acc/Dec Pattern 1 – 4
Program
Special
Acc/Dec Special
Four Acceleration times and four Deceleration times may be set up and run
individually.
Accel/Decel Time 1
–
4
may be selected using this parameter
setting or switched via threshold frequencies, or by discrete input terminal.
This parameter is used to select one of the four configured accel/decel profiles
to be used.
Settings:
1 — Acc/Dec 1
2 — Acc/Dec 2
3 — Acc/Dec 3
4 — Acc/Dec 4
Each Accel/Decel selection is comprised of an
Acceleration Time
,
Deceleration Time
, and a
Pattern
selection. Selection 1, 2, and 3 have a
Switching Frequency
setting. The
Switching Frequency
is used as a threshold
frequency that, once reached, the ASD switches to the next higher
Acc/Dec
selection (i.e., 1 to 2, 2 to 3, or 3 to 4).
Switching Frequency
settings are also
used during deceleration. A switching frequency setting is not required for
Acc/Dec 4
.
Acc/Dec 1
is set up using parameters
(Dec Time),
(Pattern), and
(Switching Frequency).
Acc/Dec 2
is set up using parameters
(Dec Time),
(Pattern), and
(Switching Frequency).
Acc/Dec 3
is set up using parameters
(Acc Time),
(Dec Time),
(Pattern), and
(Switching Frequency).
Acc/Dec 4
is set up using parameters
(Acc Time),
(Pattern).
This parameter (
) is used to manually select
Acc/Dec 1
–
4
.
To switch using the
Terminal Board
, assign the functions
Acc/Dec Switching
1
and
Acc/Dec Switching 2
to two discrete input terminals. Activation
combinations of the two terminals result in the
Acc/Dec
1 – 4
selections as
.
shows the setup requirements and the resulting output frequency
response when using
Switching Frequency
settings to control the
Acc/Dec
response of the ASD output.
While operating using
S-Pattern 1
, the system performance may be further
enhanced by the adjustment of parameters
. These settings provide
for upper and lower
Acc/Dec
limit adjustments. These settings are used to
extend or shorten the upper or lower
Acc/Dec
curve.
Note:
If operating from the
Hand
mode, press
Esc
from the
Frequency
Command
screen to access this parameter.
Direct Access Number — F504
Parameter Type —
Selection List
Factory Default —
1
Changeable During Run —
Yes
Figure 37. Using Acc/Dec Switching.
Accel/Decel Switching Frequency 1
Program
Special
Accel/Decel Special
This parameter sets the frequency at which the acceleration control is switched
from the
Accel 1
profile to the
Accel 2
profile during a multiple-acceleration
profile configuration.
Direct Access Number — F505
Parameter Type —
Numerical
Factory Default —
30.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Table 5
. Using combinations of discrete
terminal activations Accel/Decel profiles
1 – 4 may be selected.
Acc/Dec Switching Truth Table
A/D SW 1
A/D SW 2 Acc/Dec # Out
0
0
1
0
1
2
1
0
3
1
1
4
1 = Discrete terminal activation.
1
— Accel time 1 (
setting)
2
— Accel time 2 (
setting)
3
— Accel time 3 (
setting)
4
— Accel time 4 (
setting)
5
— Decel time 4 (
setting)
6
— Decel time 3 (
setting)
7
— Decel time 2 (
setting)
8
— Decel time 1 (
setting)
Summary of Contents for P9
Page 2: ......
Page 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Page 4: ......
Page 305: ......