P9 ASD Installation and Operation Manual
231
My Function Frequency Data 4
Program
My Function
My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the
My Function Frequency Data 4
.
The analog signal is selected using the
Input Setting
.
Direct Access Number — F926
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 200.00
Units — %
My Function Frequency Data 5
Program
My Function
My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the
My Function Frequency Data 5
.
The analog signal is selected using the
Input Setting
.
Direct Access Number — F927
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 200.00
Units — %
My Function Time Data 1
Program
My Function
My Function Data
This parameter is used to set the response delay of the
My Function Time
Data 1
terminal.
The applied discrete input signal must be present at the input terminal of the
P9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F928
Parameter Type —
Numerical
Factory Default —
0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 2
Program
My Function
My Function Data
This parameter is used to set the response delay of the
My Function Time
Data 2
terminal.
The applied discrete input signal must be present at the input terminal of the
P9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F929
Parameter Type —
Numerical
Factory Default —
0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 3
Program
My Function
My Function Data
This parameter is used to set the response delay of the
My Function Time
Data 3
terminal.
The applied discrete input signal must be present at the input terminal of the
P9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F930
Parameter Type —
Numerical
Factory Default —
0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds