Figure 4. The
Grounding Capacitor
Switch
is used on typeforms
230-volt
0.75 HP to 10 HP and the 25 and 30 HP/
460-volt
1.0 HP to 25 HP.
The value may be set to
Maximum
(default setting) or to
Zero
by pushing or
pulling the switch actuator, respectively.
Figure 5. The
Grounding Capacitor
Switch
is used on typeforms
230-volt
15 HP and 20 HP and the 40 HP to 60
HP/
460-volt
30 HP to 100 HP.
The value may be set to
Large
(default setting) or
Small
by pushing
or pulling the switch actuator,
respectively.
Figure 6. The
Grounding Capacitor
Bar
is used on typeforms
230-volt
75
HP to 125 HP/
460-volt
125 HP and
the 150 HP.
The value may be set to
Large
or
Small
(default setting) by connecting
or disconnecting the switching bar,
respectively.
Figure 7. pg. 19The
Grounding
Capacitor Screw
is used on
typeforms
460-volt
200 HP and
above.
The value may be set to
Large
or
Small
(default setting) by placing the
screw in the
A
position or by placing
the screw in the
B
position,