78
P9 ASD Installation and Operation Manual
Command Mode Selection
Program
Fundamental
Standard Mode Selection
The
Command Mode Selection
establishes the source of the command input
for the ASD. Command inputs include
Run
,
Stop
,
Forward
, etc. The
Override
feature may supersede the
Command Mode Selection
setting (see
Mode and Frequency Mode Control on pg. 38
Settings:
0 — Terminal Block
2 — EOI (Keypad)
3 — RS485
4 — Communication Option Board
Direct Access Number — F003
Parameter Type —
Selection List
Factory Default —
Terminal Block
Changeable During Run —
No
Frequency Mode 1
Program
Fundamental
Standard Mode Selection
The
Frequency Mode 1
setting establishes the source of the frequency-control
input for the ASD. The
Frequency Mode 2
setting or the
Override
feature may
supersede the
Frequency Mode 1
setting.
Note:
Only
Bolded
items from the
Settings
list below may be placed in
the
Override Mode
. See the section titled
Frequency Mode Control on pg. 38
for additional information on
the
Override
feature.
Settings:
1 —
V/I
2 — RR
3 — RX
5 —
EOI
(Keypad)
6 —
RS485
7 — Communication Option Board
8 — RX2 Option (AI1)
9 —
Option V/I
10 — UP/DOWN Frequency
11 — Pulse Input (Option)
12 — Pulse Input (Motor CPU)
13 — Binary/BCD Input (Option)
Direct Access Number — F004
Parameter Type —
Selection List
Factory Default —
RR
Changeable During Run —
No
Summary of Contents for P9
Page 2: ......
Page 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Page 4: ......
Page 305: ......