142
P9 ASD Installation and Operation Manual
Panel Torque Bias
Program
Torque
Torque Control
, this parameter establishes the torque bias setting to
which the setting of
will either add to or subtract from to produce the final
torque value used to carry out the
Braking Mode Selection
function of
.
Direct Access Number — F343
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — -250.00
Maximum — +250.00
Units — %
Panel Torque Gain
Program
Torque
Torque Control
, this parameter sets the sensitivity of the torque control
for the
Braking Mode Selection
Direct Access Number — F344
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.00
Units — %
Release Time
Program
Torque
Torque Control
, this parameter sets the time that the brake will hold after
the requirements of the
Braking Mode Selection
function of
have been
met.
Direct Access Number — F345
Parameter Type —
Numerical
Factory Default —
0.05
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Creeping Frequency
Program
Torque
Torque Control
, upon receiving a
Stop
command while running, this
parameter sets an output frequency to be provided for the duration of the time
setting of
Direct Access Number — F346
Parameter Type —
Numerical
Factory Default —
3.00
Changeable During Run —
Yes
Minimum —
Setting
Maximum — 20.0
Units — Hz
Creeping Time
Program
Torque
Torque Control
Once the
Creep
function of
is activated, this parameter determines the
duration of activation of the
Creep
function.
Direct Access Number — F347
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 2.50
Units — Seconds