P9 ASD Installation and Operation Manual
153
(Virtual Linear Pump) Mode Switch
Program
Virtual Linear Pump
Virtual Linear Pump Settings
This parameter is enabled for use by completing the
Virtual Linear Pump
Setup Wizard
.
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes if feedback is used or not.
Select the command source or the feedback source for operating in the
Direct
or
Process
. The default selection for each may be
used.
Note:
If
is set to use
V/I
as the command source,
DO NOT
set
this parameter to
Process Hold
. Doing so will result in an error
message (V/I cannot be used for both functions).
Note:
The selected setting for this parameter will be retained when the
Virtual Linear Pump
function is turned on or off using a discrete
input terminal set to
Virtual Linear Pump Enable/Disable
.
Settings:
0 — Disabled
1 — Direct Mode (No Feedback Used)
2 — Process Hold (V/I Feedback Used)
255 — Setup
Direct Access Number — F390
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
(Virtual Linear Pump) Application Type
Program
Virtual Linear Pump
Virtual Linear Pump Settings
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the process variable measurement type.
Settings:
0 — Pressure
1 — Flow
2 — Level
Direct Access Number — F391
Parameter Type —
Selection List
Factory Default —
Pressure
Changeable During Run —
No
(Virtual Linear Pump) Transducer Output Type/Range
Program
Virtual Linear Pump
Virtual Linear Pump Settings
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the transducer output signal type and range for
Virtual Linear
Pump
operation.
Note:
This parameter is scaled at
for either selection and
requires no user intervention.
Settings:
0 — 0 – 20 mA
1 — 4 – 20 mA
2 — 0 – 10 V
3 — 0 – 5 V
Direct Access Number — F392
Parameter Type —
Selection List
Factory Default —
0 – 20 mA
Changeable During Run —
No