P9 ASD Installation and Operation Manual
107
V/I Input Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
V/I
input terminal when
the
V/I
terminal is used as the control input while operating in the
Speed
Control
mode.
This parameter sets
V/I Input Point 1 Frequency
and is the frequency that is
associated with the setting of
V/I Input Point 1 Setting
when operating in the
Speed Control
mode.
See
V/I Input Point 1 Setting
) for additional information on this
parameter.
Direct Access Number — F202
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
V/I Input Point 2 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
V/I
input terminal when
the
V/I
terminal is used as the control input while operating in the
Speed
Control
mode
or the
Torque Control
mode.
This parameter sets the
V/I
input level that is associated with
V/I Input Point 2
Frequency
when operating in the
Speed
control mode or is associated with the
V/I Input Point 1 Rate
when operating in the
Torque Control
mode.
This value is entered as 0% to 100% of the
V/I
input signal range.
See
V/I Input Point 1 Setting
) for additional information on this
parameter when used for
Speed
control.
See
V/I Input Point 1 Rate
) for additional information on this parameter
when used for
Torque
Control
.
Direct Access Number — F203
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
V/I Input Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
V/I
input terminal when
the
V/I
terminal is used as the control input while operating in the
Speed
Control
mode.
This parameter sets
V/I Input Point 2 Frequency
and is the frequency that is
associated with the setting of
V/I Input Point 2 Setting
when operating in the
Speed Control
mode.
See
V/I Input Point 1 Setting
) for additional information on this
parameter.
Direct Access Number — F204
Parameter Type —
Numerical
Factory Default —
60.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz