204
P9 ASD Installation and Operation Manual
AM Terminal Function
Program
Terminal
Analog Output Terminals
This setting determines the output function of the
AM
analog output terminal.
The
AM
output terminal produces an output voltage that is proportional to the
magnitude of the function assigned to this terminal. The available assignments
for this output terminal are listed in
To read
Voltage
at this terminal, connect a 100 – 500
resistor from AM (+) to
CC
. The voltage is read across the 100 – 500
resistor.
AM Terminal Setup Parameters
— Set AM Function
— Calibrate AM Terminal
— Output Response Polarity Selection
— Set Zero Level
Direct Access Number — F670
Parameter Type —
Selection List
Factory Default —
Output Frequency
Changeable During Run —
Yes
AM Output Terminal Adjustment
Program
Terminal
Analog Output Terminals
This parameter is used to calibrate the
AM
analog output.
To calibrate the
AM
analog output, connect an ammeter as described at
When the ASD is running at a known value (e.g., output frequency), adjust this
parameter until the associated function of
output at the
AM
output terminal.
See
for additional information on this parameter.
Direct Access Number — F671
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
M