P9 ASD Installation and Operation Manual
203
V/I Analog Input Loss Response
Program
Terminal
Input Special Functions
This parameter is used to provide a system disposition in the event of the loss of
the
V/I
input signal.
The system will either trip, run the speed set at
, or run at the
Direct
mode.
Note:
must be configured to use the preset speed
selection.
Settings:
0 — Trip
1 — Preset Speed 14
2 — Direct Mode Speed Setpoint (Run at
setting)
Direct Access Number — F644
Parameter Type —
Selection List
Factory Default —
Trip
Changeable During Run —
No
Adding Input Selection
Program
Feedback
Override Control
This parameter
Enables/Disables
the feature that allows for the external
adjustment of the
Output Frequency
.
Selecting either of the input methods listed enables this feature. The selected
input is used as a modifier of the programmed
Output Frequency
.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
5 — EOI (Keypad)
6 — RS485 (2-Wire)
7 — Communication Option Board
8 — RX2 Option (AI1)
9 — Option V/I
10 — UP/DOWN Frequency (Terminal Board)
11 — Pulse Input (Option)
12 — Pulse Input (Motor CPU)
13 — Binary/BCD Input (Option)
Direct Access Number — F660
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Multiplying Input Selection
Program
Feedback
Override Control
This parameter
Enables/Disables
the feature that allows for the external
adjustment of the commanded frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a multiplier of the commanded frequency.
If
Setting
(
) is selected, the
the multiplier of the commanded frequency.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — Setting (
5 — RX2 Option (AI1)
Direct Access Number — F661
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes