P9 ASD Installation and Operation Manual
207
FM Bias Adjustment
Program
Terminal
Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the
FM
terminal.
Set the function of
to zero and then set this parameter to zero for proper
operation.
See
for additional information on this parameter.
Direct Access Number — F683
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -10.0
Maximum — +100.0
Units — %
AM Output Gradient Characteristic
Program
Terminal
Analog Output Terminals
This parameter sets the output response polarity of the
AM
output terminal.
The
AM
output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See
for additional information on this parameter.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F685
Parameter Type —
Selection List
Factory Default —
Plus
Changeable During Run —
Yes
AM Bias Adjustment
Program
Terminal
Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the
AM
terminal.
to zero and then set this parameter to zero for
proper operation.
See
for additional information on this parameter.
Direct Access Number — F686
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -10.0
Maximum — +100.0
Units — %
MON 1 Voltage/Current Output Switching
Program
Terminal
Analog Output Terminals
This parameter is used to set the output signal type of the
MON1
output
terminal.
Settings
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
Direct Access Number — F688
Parameter Type —
Selection List
Factory Default —
0 – 10V
Changeable During Run —
Yes
MON 1 Output Gradient Characteristic
Program
Terminal
Analog Output Terminals
This parameter sets the output response polarity of the
MON1
output terminal.
The
MON1
output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See
for additional information on this parameter.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F689
Parameter Type —
Selection List
Factory Default —
Plus
Changeable During Run —
Yes