P9 ASD Installation and Operation Manual
79
FM Terminal Function
Program
Terminal
Analog Output Terminals
This setting determines the output function of the
FM
analog output terminal.
The
FM
output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal (select
current or voltage at
). The available assignments for this output terminal
are listed in
Note:
If the monitored item has a positive and a negative component,
use the
Expansion I/O Card 2
(P/N ETB004Z). See the
Expansion IO Card Option 2
instruction manual (P/N 58686)
for additional information on the function of the option card.
To read
Voltage
at this terminal, connect a 100 – 500
resistor from FM (+) to
CC
(-). The voltage is read across the 100 – 500
resistor.
To read
Current
at this terminal, connect a 100 – 500
resistor in series from
FM (+), through the current meter, to
CC
(-).
FM Terminal Setup Parameters
— Set FM Function
— Calibrate FM Terminal
— Voltage/Current Output Switching Selection
— Output Response Polarity Selection
— Set Zero Level
Direct Access Number — F005
Parameter Type —
Selection List
Factory Default —
Output Frequency
Changeable During Run —
Yes
FM Output Terminal Adjustment
Program
Terminal
Analog Output Terminals
This parameter is used to calibrate the
FM
analog output.
To calibrate the
FM
analog output, connect a meter (current or voltage) as
With the ASD running at a known value (e.g., output frequency), adjust this
parameter until the assigned function produces the desired DC level output at
the
FM
output terminal.
See
for additional information on this parameter.
Direct Access Number — F006
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
M