186
GX9 ASD Installation and Operation Manual
Overload Reduction Start Frequency
Program
Protection
Overload
This parameter is primarily used with V/f motors. It is used to reduce the
starting frequency at which the
Overload Reduction
function begins and is
useful during extremely low-speed motor operation.
During very low-speed operation the cooling efficiency of the motor decreases.
Lowering the start frequency of the
Overload Reduction
function aides in
minimizing the generated heat and precluding an
Overload
trip.
This function is useful in loads such as fans, pumps, and blowers that have the
square reduction torque characteristic.
Set parameter
to the desired
Overload Time Limit
.
Direct Access Number — F606
Parameter Type —
Numerical
Factory Default —
6.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Motor 150% Overload Time Limit
Program
Protection
Overload
This parameter establishes a time that the motor may operate at 150% of its
rated current before tripping. This setting applies the time/150% reference to
the individual settings of each motor (e.g., this setting references 150% of the
setting for the 1 motor).
The unit will trip sooner than the time entered here if the overload is greater
than 150%.
Direct Access Number — F607
Parameter Type —
Numerical
Factory Default —
600
Changeable During Run —
Yes
Minimum — 10
Maximum — 2400
Units — Seconds
Suppression of Inrush Current Timing
Program
Protection
Special Protection Parameters
The startup inrush current may be suppressed. This parameter
Enables/
Disables
the inrush current suppression function.
Settings:
0 — (Disabled)
1 — (Enabled)
Direct Access Number — F609
Parameter Type —
Selection List
Factory Default —
0
(Disabled
)
Changeable During Run —
No
Minimum — 0
Maximum — 1
Low-Current Trip Selection
Program
Protection
Low-Current Settings
This parameter
Enables/Disables
the low-current trip feature.
When enabled, the ASD will trip on a low-current fault if the output current of
the ASD falls below the level defined at
and remains there for the time set
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F610
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Low-Current Detection Current
Program
Protection
Low-Current Settings
With the
Low-Current Trip
) parameter is enabled, this function sets the
low-current trip threshold.
The threshold value is entered as a percentage of the maximum rating of the
ASD.
Direct Access Number — F611
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.00
Units — %
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......