GX9 ASD Installation and Operation Manual
135
Search Method
Program
Protection
Retry/Restart
In the event of a momentary power outage, this parameter may be used to set
the starting point (frequency) of the scanning signal that is used to determine
the rotor speed or this parameter may be used to select the method used to
search for the speed of the rotor.
See F301 for additional information on this parameter.
Settings:
0 — Normal
1 — Start from 0.0 Hz
2 — Start from Running Frequency
3 — Option Board
4 — PG
Direct Access Number — F314
Parameter Type —
Selection List
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Search Inertia
Program
Protection
Retry/Restart
After a momentary power loss or the momentary loss of the
ST
-to-
CC
connection, this parameter sets the time for the commanded torque to reach its
programmed setting during the automatic restart. This function is in effect so
long as the
Retry/Restart
Settings:
0 — 0.5 Second (fast)
1 — 1.0 Second (standard)
2 — 1.5 Seconds
3 — 2.0 Seconds
4 — 2.5 Seconds
5 — 3.0 Seconds
6 — 3.5 Seconds
7 — 4.0 Seconds
8 — 4.5 Seconds
9 — 5.0 Seconds (slow)
Direct Access Number — F315
Parameter Type —
Selection List
Factory Default —
1.0 (Standard)
Changeable During Run —
No
Units — Seconds
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......