GX9 ASD Installation and Operation Manual
97
OUT2 On Delay
Program
Terminal
Output Terminal Delays
This parameter delays the closing of the
OUT2
(
A
&
C
) output terminals by the
programmed value (see waveforms at
The delay may be increased to prevent relay chatter.
Direct Access Number
— F151
Parameter Type —
Numerical
Factory Default —
2
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
FL On Delay
Program
Terminal
Output Terminal Delays
This parameter delays the closing of the
FL
output terminals by the
programmed value (see waveforms at
The delay may be increased to prevent relay chatter.
Direct Access Number — F152
Parameter Type —
Numerical
Factory Default —
2
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
OUT4 On Delay
Program
Terminal
Output Terminal Delays
This parameter delays the closing of the
OUT4
output terminals by the
programmed value (see waveforms at
The delay may be increased to prevent relay chatter.
Direct Access Number — F153
Parameter Type —
Numerical
Factory Default —
2
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
OUT5 On Delay
Program
Terminal
Output Terminal Delays
This parameter delays the closing of the
OUT5
output terminals by the
programmed value (see waveforms at
The delay may be increased to prevent relay chatter.
Direct Access Number — F154
Parameter Type —
Numerical
Factory Default —
2
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
OUT6 On Delay
Program
Terminal
Output Terminal Delays
This parameter delays the closing of the
OUT6
output terminals by the
programmed value (see waveforms at
The delay may be increased to prevent relay chatter.
Direct Access Number — F155
Parameter Type —
Numerical
Factory Default —
2
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
OUT7 On Delay
Program
Terminal
Output Terminal Delays
This parameter delays the closing of the
OUT7
output terminals by the
programmed value (see waveforms at
The delay may be increased to prevent relay chatter.
Direct Access Number
— F156
Parameter Type —
Numerical
Factory Default —
2
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......