GX9 ASD Installation and Operation Manual
159
RX Input Gain
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine tune the gain of the
RX
input terminal when this
terminal is used as the control input while operating in the
Speed Control
mode
or the
Torque Control
mode.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.
Direct Access Number — F475
Parameter Type —
Numerical
Factory Default —
141
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
RX2 Input Bias
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine tune the bias of the
RX2
terminal when this
terminal is used as the control input while operating in the
Speed Control
mode
or the
Torque Control
mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and adjusting this
setting to provide a zero output from the ASD.
Direct Access Number — F476
Parameter Type —
Numerical
Factory Default —
99
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
RX2 Input Gain
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine tune the gain of the
RX2
terminal when this
terminal is used as the control input while operating in the
Speed Control
mode
or the
Torque Control
mode.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.
Direct Access Number — F477
Parameter Type —
Numerical
Factory Default —
141
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Exciting Strengthening Coefficient
Program
Special
Special Parameters
This parameter determines the rate at which the excitation current is allowed to
go from zero to saturation and is enabled at
Direct Access Number — F480
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Selection for Over-Exciting Cooperation
Program
Special
Special Parameters
This parameter determines the method used to control the rate that the
excitation current is allowed to reach saturation. If
Effective
is selected, the
preset
Torqu
e
Control
or
Speed
Control
settings will determine the rate that
the motor reaches excitation saturation.
Settings:
0 — Effective
1 — Applied by
Direct Access Number — F481
Parameter Type —
Selection List
Factory Default —
Effective
Changeable During Run —
Yes
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......