22
GX9 ASD Installation and Operation Manual
RR
— The default function assigned to this terminal is
Frequency Mode 1
. The
RR
terminal accepts
an analog 0 – 10 VDC input signal that is used to control the function assigned to this terminal. This
input terminal may be programmed to control the speed or torque of the motor via an amplitude setting
or regulate by setting a limit. The gain and bias of this terminal may be adjusted for application-specific
suitability (see
).
RX
— The default function assigned to this terminal is
Torque Command
. The
RX
terminal accepts a
±10 VDC input signal that is used to control the function assigned to this terminal. This input terminal
may be programmed to control the speed or torque of the motor via an amplitude setting or regulate by
setting a limit. The gain and bias of this terminal may be adjusted for application-specific suitability
(see
II
— The
II
terminal is an isolated current input that is used to control the speed or torque of the motor.
Return at
II
(-). Select
VI/II
at for speed control or select
VI/II
for torque control. The
II
terminal receives a 0 – 20 mA input signal that controls the output 0.0 –
Maximum Frequency
output
or the -250% – 250% torque output of the ASD. Terminal scaling is accomplished via
. The
gain and bias of this terminal may be adjusted for application-specific suitability (see
and
Note:
The
VI
terminal or the
II
terminal may be used to control the speed or torque of the
motor. Selecting
VI/II
at parameter
enables both terminals for use, but both
cannot be used simultaneously. The user connects the proper input (current or
voltage) to the appropriate terminal to be used for control.
VI
— The
VI
terminal is an isolated voltage input that is used to control the speed or torque of the
motor. Select
VI/II
for speed control or select
VI/II
for torque control. The
VI
terminal
receives a 0 – 10 VDC input signal that controls the output 0.0 –
Maximum Frequency
output or the
-250% – 250% torque output of the ASD. Terminal scaling is accomplished via
. The gain
and bias of this terminal may be adjusted for application-specific suitability (see
and
).
Note:
The
VI
terminal or the
II
terminal may be used to control the speed or torque of the
motor. Selecting
VI/II
at parameter
enables both terminals for use, but both
cannot be used simultaneously. The user connects the proper input (current or
voltage) to the appropriate terminal to be used for control.
P24
— +24 VDC at 200 mA power supply for customer use.
PP
— The function of output
PP
is to provide a 10 VDC/10 mADC (max.) output that may be divided
using a potentiometer. The tapped voltage is applied to the
RR
input to provide manual control of the
RR
programmed function.
OUT1
— The default function assigned to this terminal is
External Device 1
. The function as
External
Device 1
is to activate/deactivate an auxiliary motor once the
Virtual Linear Pump
level has remained
above the
Maximum
threshold
setting
or below the
Minimum
threshold
setting
for the time setting of
. The
OUT1
terminal is rated at 2 A/120 VAC and 2 A/30 VDC and may be set to any of the
(see
OUT2
— The default function assigned to this terminal is
External Device 2
. The function as
External
Device 2
is to activate/deactivate an auxiliary motor once the control level of the
Virtual Linear Pump
settings has remained above the
Maximum
threshold or below the
Minimum
threshold
settings
for the
. The
OUT2
terminal is rated at 2 A/120 VAC and 2 A/30 VDC and may be set to
any of the functions listed in
(see
FP
— The default function of this output terminal is to output a series of pulses at a rate that is a
function of the ASD output frequency (50 mA max. at 1.0 kHz to 43.3 kHz). As the output frequency of
the ASD goes up so does the
FP
output pulse rate. This terminal may be programmed to provide an
output pulse rate that is proportional to the magnitude of the user-selected item from
For further information on this terminal, see parameter
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......