GX9 ASD Installation and Operation Manual
115
RX Input Point 1 Torque
Program
Torque
Setpoints
This parameter is used to set the gain and bias of the
RX
input terminal when
the
RX
terminal is used as the control input while operating in the
Torque
Control
mode.
The bias and gain of the
RX
respectively.
RX Torque Control Setup
Perform the following setup to allow the system to receive
Torque Control
input at the
RX
input terminal:
• Program
Fundamental
Standard Mode Selection
Frequency Mode
RX
.
• Program
Fundamental
Standard Mode Selection
Command Mode
Selection
Terminal Board
.
• Set
RX Input Point 1 Torque
(
).
• Set
RX Reference Point 1
) — the input analog signal level that
corresponds to the torque setting at
RX Input Point 1 Torque
.
• Set
RX Input Point 2 Torque
(
).
• Set
RX Reference Point 2
) — the input analog signal level that
corresponds to the speed setting at
RX Input Point 2 Torque
.
• Provide a
Run
command (F and/or R).
Torque Control
is accomplished by establishing an associated
V/f
output
pattern for a given
RX
input level.
Once set, as the
RX
input voltage changes, the ASD output speed and/or torque
will vary in accordance with the above settings.
This parameter sets
RX Input Point 1 Torque
and is the output torque value
that is associated with the setting of
RX Reference Point 1
when operating in
the
Torque Control
mode.
This value is entered as -250% to +250% of the rated torque.
Direct Access Number — F220
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — -250.00
Maximum — +250.00
Units — %
Torque Settings
RX Input Point 2 Torque
Program
Torque
Setpoints
This parameter is used to set the gain and bias of the
RX
input terminal when
the
RX
terminal is used as the control input while operating in the
Torque
Control
mode.
Torque Control
is accomplished by establishing an associated
V/f
output
pattern for a given
RX
input level.
This parameter sets
RX Input Point 2 Torque
and is the output torque value
that is associated with the setting of
RX Reference Point 2
when operating in
the
Torque Control
mode.
This value is entered as -250% to +250% of the rated torque.
See
RX Input Point 1 Torque
(
) for more information on this setting.
Direct Access Number — F221
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — -250.00
Maximum — +250.00
Units — %
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......