GX9 ASD Installation and Operation Manual
157
Torque Limit Mode (Speed Dependent)
Program
Torque
Torque Limit Settings
Select
Standard
to allow for the output speed of the ASD to vary as a function
of load variations to maintain a user-set output torque.
Settings:
0 — Standard
1 — No Speed Cooperation
Direct Access Number — F451
Parameter Type —
Selection List
Factory Default —
Standard
Changeable During Run —
Yes
Power Running Stall Continuous Trip Detection Time
Program
Protection
Stall
This parameter is used to extend the
Over-Voltage Limit Operation
and the
Motor Overload Protection Configuration
) time settings.
Direct Access Number — F452
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 1.00
Units — Seconds
Regenerative Braking Stall Prevention Mode Selection
Program
Protection
Stall
This function of this parameter is to disable the
Over-Voltage Limit Operation
)
and the
Motor Overload Protection Configuration
(
) function
during regeneration only.
Application-specific conditions may occur that warrant disabling the
Stall
function during regeneration.
Settings:
0 — Enabled
1 — Disabled
Direct Access Number — F453
Parameter Type —
Selection List
Factory Default —
Enabled
Changeable During Run —
Yes
Current Differential Gain
Program
Special
Special Parameters
This parameter determines the degree that the current differential function
affects the output signal. The larger the value entered here, the more
pronounced the
Current Differential Gain
.
Direct Access Number — F454
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 327.67
VI/II Input Bias
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine-tune the bias of the
VI/II
terminals.
Note:
See note on
VI/II
terminal.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and adjusting this
setting to provide an output of zero from the ASD.
Direct Access Number — F470
Parameter Type —
Numerical
Factory Default —
99
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......