Acceleration/Deceleration Pattern 1 – 4 Selection
Program
Special
Accel/Decel (1 – 4) Settings
Four Acceleration times and four Deceleration times may be set up and run
individually.
Accel/Decel Time 1
–
4
may be selected using this parameter
setting or switched via threshold frequencies, or by discrete input terminal.
This parameter is used to select one of the four configured accel/decel profiles
to be used.
Settings:
1 — Acc/Dec 1
2 — Acc/Dec 2
3 — Acc/Dec 3
4 — Acc/Dec 4
Each Accel/Decel selection is comprised of an
Acceleration Time
,
Deceleration Time
, and a
Pattern
selection. Selection 1, 2, and 3 have a
Switching Frequency
setting. The
Switching Frequency
is used as a threshold
frequency that, once reached, the ASD switches to the next higher
Acc/Dec
selection (i.e., 1 to 2, 2 to 3, or 3 to 4).
Switching Frequency
settings are also
used during deceleration. A switching frequency setting is not required for
Acc/Dec 4
.
Acc/Dec 1
is set up using parameters
(Dec Time),
(Pattern), and
(Switching Frequency).
Acc/Dec 2
is set up using parameters
(Dec Time),
(Pattern), and
(Switching Frequency).
Acc/Dec 3
is set up using parameters
(Acc Time),
(Dec Time),
(Pattern), and
(Switching Frequency).
Acc/Dec 4
is set up using parameters
(Acc Time),
(Pattern).
This parameter (F504) is used to manually select
Acc/Dec 1
–
4
.
To switch using the
Terminal Board
, assign the functions
Acc/Dec Switching
1
and
Acc/Dec Switching 2
to two discrete input terminals. Activation
combinations of the two terminals result in the
Acc/Dec
1 – 4
selections as
.
shows the setup requirements and the resulting output frequency
response when using
Switching Frequency
settings to control the
Acc/Dec
response of the ASD output.
While operating using
S-Pattern 1
the system performance may be further
enhanced by the adjustment of parameters
. These settings provide
for upper and lower
Acc/Dec
limit adjustments. These settings are used to
extend or shorten the upper or lower
Acc/Dec
curve.
Note:
If operating from the
Local
mode, press
Esc
from the
Frequency
Command
screen to access this parameter.
Direct Access Number — F504
Parameter Type —
Selection List
Factory Default —
Selection 1
Changeable During Run
—
Yes
Figure 35. Using Acc/Dec Switching.
Acceleration/Deceleration Switching Frequency 1
Program
Special
Accel/Decel Special
This parameter sets the frequency at which the acceleration control is switched
from the
Accel 1
profile to the
Accel 2
profile during a multiple-acceleration
profile configuration.
Direct Access Number — F505
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum —
Max. Freq.
Units — Hz
Table 7
. Using combinations of discrete
terminal activations Accel/Decel profiles
1 – 4 may be selected.
Acc/Dec Switching Truth Table
A/D SW 1
A/D SW 2
Acc/Dec # Out
0
0
1
0
1
2
1
0
3
1
1
4
1 = Discrete terminal activation.
1
— Accel time 1 (
setting)
2
— Accel time 2 (
setting)
3
— Accel time 3 (
setting)
4
— Accel time 4 (
setting)
5
— Decel time 4 (
setting)
6
— Decel time 3 (
setting)
7
— Decel time 2 (
setting)
8
— Decel time 1 (
setting)
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......