146
GX9 ASD Installation and Operation Manual
Speed Loop Proportional Gain
Program
Feedback
PG Settings
This parameter sets the
Proportional Gain
(sensitivity) of the drive when
monitoring the
PG
signal to control speed. The larger the value entered here,
the more sensitive the drive is to changes in the received feedback and the
quicker it responds.
Direct Access Number — F376
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 3.2
Maximum — 1000
Speed Loop Integral Gain
Program
Feedback
PG Settings
This parameter sets the response time of the
Speed Loop Integral Gain
. The
smaller the value here, the more pronounced (quicker) the effect of the integral
function.
Direct Access Number — F377
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 200.0
Motor Counter Data Selection
Program
Feedback
PG Settings
This parameter sets the pulses-per-revolution displayed at the Monitor screen
when using a shaft-mounted encoder for speed control. This setting is used for
display purposes only and does not affect the speed control of the system.
If zero is selected here then the setting at
(Electronic Gear Setting)
determines the pulses-per-revolution to be displayed at the Monitor screen.
Settings:
0 — F370 setting
1 — 256 pulses/revolution
2 — 512 pulses/revolution
3 — 1024 pulses/revolution
4 — 2048 pulses/revolution
5 — 4096 pulses/revolution
Direct Access Number — F378
Parameter Type —
Selection List
Factory Default —
Selection 0
Changeable During Run —
No
Minimum — Selection 0
Maximum — Selection 5
Speed Loop Parameter Ratio
Program
Feedback
PG Settings
Used for positioning control. Increases/decreases the ASD response time to the
received feedback.
Direct Access Number — F379
Parameter Type —
Numerical
Factory Default —
1.00
Changeable During Run —
No
Minimum — 0.01
Maximum — 10.00
Units — Seconds
Preset Speed Operation Mode
Program
Frequency
Preset Speed Modes
This parameter
Enables/Disables
the
Speed Operation Mode
when using a
preset speed. When enabled, the system uses all of the parameter settings of the
Preset Speed
being run. Otherwise, only the frequency setting is used.
Settings:
0 — Disabled (Use Frequency Command Only)
1 — Enabled (Use Direction, Acc/Dec, V/f, and Torque)
Direct Access Number — F380
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......