7. Motor Capacity
This parameter allows the user to input the full-load
capability of the motor in kilo Watts. This value is
used by the GX9 ASD to determine the motor
overload protection setting for the motor and may be
found on the nameplate of the motor.
8. Command Source
This selection establishes the source of the
Run
commands (e.g., F, R, Stop, etc.).
Settings:
0 — Terminal Board
1 — CN8 Option
2 — Common Serial (TTL)
3 — RS232/RS485
4 — Communication Card
9. Frequency Command Source
This selection establishes the source of the
Frequency
(speed) command.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2 Option
5 — CN8 Option
6 — Binary/BCD Input
7 — Common Serial (TTL)
8 — RS232/RS485
9 — Communication Card
10 — UP/DOWN Frequency
11 — Pulse Input Option
10. Display Units
This screen sets the display units for current and
voltage.
Settings:
0 — %
1 — A/V (Amp/Volt)
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......