S-Pattern Acceleration Lower-Limit Adjustment
Program
Special
Accel/Decel Special
During an
S-Pattern
1
or
2
sequence, this parameter settings modifies the
acceleration rate for the lower part of the acceleration curve by the percentage
set here.
This function is commonly used with transportation and lifting applications.
See parameter
for more information on this setting.
Direct Access Number — F506
Parameter Type —
Numerical
Factory Default —
25
Changeable During Run —
Yes
Minimum — 0
Maximum — 50
Units — %
S-Pattern Acceleration Upper-Limit Adjustment
Program
Special
Accel/Decel Special
During an
S-Pattern
1
or
2
sequence, this parameter settings modifies the
acceleration rate for the upper part of the acceleration curve by the percentage
set here.
This function is commonly used with transportation and lifting applications.
See parameter
for more information on this setting.
Direct Access Number — F507
Parameter Type —
Numerical
Factory Default —
25
Changeable During Run —
Yes
Minimum — 0
Maximum — 50
Units — %
Acceleration/Deceleration Time Lower Limit
Program
Special
Accel/Decel Special
This parameter sets the lower limit of the
Accel/Decel
time settings.
Direct Access Number — F508
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 10.00
Units — Seconds
Acceleration Time 3
Program
Special
Accel/Decel (1 – 4) Settings
This parameter specifies the time in seconds for the output of the ASD to go
from 0.0 Hz to the
Maximum Frequency
for the
3 Acceleration
profile. The
Accel/Decel pattern may be set using
. The minimum Accel/Decel time
may be set using
.
Note:
An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic
Accel/Decel
,
Stall
, and
Ridethrough
settings
may lengthen the
acceleration times.
Direct Access Number — F510
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — Acc/Dec Lower Limit
(
Maximum — 6000.00
Units — Seconds
Deceleration Time 3
Program
Special
Accel/Decel (1 – 4) Settings
This parameter specifies the time in seconds for the output of the ASD to go
from the
Maximum Frequency
to 0.0 Hz for the
3 Deceleration
profile.
The Accel/Decel pattern may be set using
. The minimum Accel/Decel
time may be set using
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic
Accel/Decel
,
Stall
, and
Ridethrough
settings
may lengthen the
deceleration times.
Direct Access Number — F511
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — Acc/Dec Lower Limit
(
Maximum — 6000.00
Units — Seconds
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......