226
GX9 ASD Installation and Operation Manual
*OH
*Over-Heat
ASD ambient temperature
excessive.
• ASD is operating at an elevated temperature.
• ASD is too close to heat-generating equipment.
• Cooling fan vent is obstructed (see
).
• Cooling fan is inoperative.
• Internal thermistor is disconnected.
OJ
Cumulative Run Timer
Run-time counter exceeded.
•
Type Reset
required; select
Clear run timer
.
OL2
Motor Overload
Load requirement exceeds the
ability of the motor.
• Improper V/f setting.
• Motor is locked.
• Continuous operation at low speed.
• Startup frequency setting adjustment required.
*OLI
*ASD Overload
Load requirement in excess of
the capability of the ASD.
• The carrier frequency is too high.
• An excessive load.
• Acceleration time is too short.
• DC damping rate is set too high.
• The motor is starting into a spinning load after a
momentary power failure.
• The ASD is improperly matched to the
application.
*OLR
*Braking Resistor
Overload
Excessive current at the
Dynamic Braking Resistor
.
• Deceleration time is too short.
• DBR configuration improperly set.
*OP
*Over-Voltage
DC bus voltage exceeds
specifications.
• ASD attempting to start into a spinning motor
after a momentary power loss.
• Incoming commercial power is above the
specified range.
• Decel time is too short.
• Voltage spikes at the 3-phase input; install
inductive filter.
• DBR required.
• DBR resistance value is too high.
• DBR function is turned off.
• Over-Voltage Stall feature is turned off.
• System is regenerating.
• Load instability.
• Disable the Ridethrough function (
).
OT
Excessive Torque
Torque requirement is in excess
of the setting of
for a time longer than the setting
of
• ASD is not correctly matched to the application.
•
or
setting is too low.
• Obstructed load.
*
Reset ignored if active.
LED
Screen
LCD
Screen
Description
Possible Causes/
Troubleshooting
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......