188
GX9 ASD Installation and Operation Manual
Over-Torque Detection Level During Regenerative Braking
Program
Protection
Over-Torque Parameters
This parameter sets the torque threshold level that is used as a setpoint for over-
torque tripping during negative torque (regen). This setting is a percentage of
the maximum rated torque of the ASD.
.
Direct Access Number — F617
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Over-Torque Detection Time
Program
Protection
Over-Torque Parameters
This parameter sets the amount of time that the over-torque condition may
exceed the tripping threshold level set at
and
before a trip occurs.
.
Direct Access Number — F618
Parameter Type —
Numerical
Factory Default —
0.50
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.0
Units — Seconds
Cooling Fan Control
Program
Protection
Special Protection Parameters
This parameter sets the cooling fan run-time command.
Settings:
0 — Automatic
1 — Always On
2 — Internal/External Temp Controlled
3 — Internal-Auto/External-Temp Controlled
4 — Internal-Temp Controlled/External-Auto
Direct Access Number — F620
Parameter Type —
Selection List
Factory Default —
Automatic
Changeable During Run —
Yes
Cumulative Operation Time Alarm Setting
Program
Protection
Special Protection Parameters
This parameter sets a run-time value that, once exceeded, closes a discrete
output contact. The output signal may be used to control external equipment or
used to engage a brake.
Associate the
Total-Operation-Hours Alarm
setting of
a discrete output contactor.
Note:
The time displayed is 1/10th of the actual time (0.1 hr. = 1.0 hr.).
Direct Access Number — F621
Parameter Type —
Numerical
Factory Default —
175.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 999.9
Units — Hours (X 10)
Abnormal Speed Detection Time
Program
Protection
Abnormal Speed Settings
This parameter sets the time that an over-speed condition must exist to cause a
trip.
This parameter functions in conjunction with the settings of
.
Direct Access Number — F622
Parameter Type —
Numerical
Factory Default —
10.00
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 100.00
Units — Seconds
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......