GX9 ASD Installation and Operation Manual
99
OUT6 OFF Delay
Program
Terminal
Output Terminal Delays
This parameter delays the opening of the
OUT6
output terminals by the
programmed value (see waveforms at
The delay may be increased to prevent relay chatter.
Direct Access Number
— F165
Parameter Type —
Numerical
Factory Default —
2
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
OUT7 OFF Delay
Program
Terminal
Output Terminal Delays
This parameter delays the opening of the
OUT7
output terminals by the
programmed value (see waveforms at
The delay may be increased to prevent relay chatter.
Direct Access Number — F166
Parameter Type —
Numerical
Factory Default —
2
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
Base Frequency 2
Program
Motor
Motor Set 2
The
Base Frequency 2
setting is the frequency at which the output voltage of
the ASD reaches its maximum setting. The
Base Frequency Voltage 2
parameter is set at
This parameter is used only when the parameters for
Motor Set
2
are
configured and selected.
Motor Set
2
may be selected by a properly configured
input terminal (see
For proper motor operation, the
Base Frequency
should be set for the
nameplated frequency of the motor.
Direct Access Number — F170
Parameter Type —
Numerical
Factory Default —
60.0
Changeable During Run —
Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz
Base Frequency Voltage 2
Program
Motor
Motor Set 2
The
Base Frequency Voltage 2
setting is the
Motor
2
output voltage at the
Base Frequency
). Regardless of the programmed value, the output
voltage cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the
Supply Voltage Correction
setting (
).
This parameter is used only when the parameters for
Motor Set
2
are
configured and selected.
Motor Set
2
may be selected by a properly configured
input terminal (see
Direct Access Number — F171
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 700.0
Units — Volts
Manual Torque Boost 2
Program
Motor
Motor Set 2
The
Manual Torque Boost 2
function is used to increase the low frequency
torque for high inertia loads by increasing the output voltage at frequencies
below ½ of the
Base Frequency 2
setting
See parameter
(Manual Torque Boost 1) for an explanation of torque
boost.
This parameter is used only when the parameters for
Motor Set
2
are
configured and selected.
Motor Set
2
may be selected by a properly configured
input terminal (see
Direct Access Number — F172
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.00
Units — %
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......