110
GX9 ASD Installation and Operation Manual
RR Reference Point 1
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RR
terminal when the
RR
terminal is used as the control input while operating in the
Speed Control
mode
or the
Torque Control
mode.
This parameter sets the
RR
input level that is associated with the
RR Input
Point 1 Frequency
setting when operating in the
Speed
control mode or is
associated with the
RR Input Point 1 Torque
setting when operating in the
Torque Control
mode.
The bias and gain of the
RR
respectively.
RR Speed Control Setup
Perform the following setup to allow the system to perform
Speed
control from
the
RR
terminal:
• Set
RR Input Point 1 Frequency
(
• Set
RR Reference Point 1
) — the input analog signal level that
corresponds to the frequency setting at
RR Input Point 1 Frequency
.
• Set
RR Input Point 2 Frequency
(
).
• Set
RR Reference Point 2
) — the input analog signal level that
corresponds to the frequency setting at
RR Input Point 2 Frequency
.
• Program
Fundamental
Standard Mode Selection
Frequency Mode
1
RR
.
• Program
Fundamental
Standard Mode Selection
Command Mode
Selection
Terminal Board
.
• Provide a
Run
command (F and/or R).
Once set, as the
RR
voltage changes, the output frequency of the ASD will vary
in accordance with the above settings.
This parameter value is entered as 0% to 100% of the
RR
signal range.
Direct Access Number — F210
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.00
Units — %
Frequency Settings
RR Input Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RR
terminal when the
RR
terminal is used as the control input while operating in the
Speed Control
mode.
This parameter sets
RR Input Point 1 Frequency
and is the frequency that is
associated with the setting of
RR Reference Point 1
when operating in the
Speed Control
mode.
See
RR Reference Point 1
) for more information on this setting.
Direct Access Number — F211
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum —
Max. Freq.
Units — Hz
R
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......