150
GX9 ASD Installation and Operation Manual
Motor Constant 2 (secondary resistance)
Program
Motor
Vector Motor Model
This parameter is the measurement of the rotor resistance and is considered a
Motor Constant
(unchanging). This value is used in conjunction with other
constants to tune the motor.
This setting (motor tuning) is required to use the
Vector Control
,
Automatic
Torque Boost
, or
Automatic Energy-saving
functions.
Direct Access Number — F403
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Minimum — 0.00
Maximum — Open
Units — m
Motor Constant 3 (exciting inductance)
Program
Motor
Vector Motor Model
This parameter is used to input the excitation inductance for the motor. This
value is used in conjunction with other constants to tune the motor.
This setting (motor tuning) is required to use the
Vector Control
,
Automatic
Torque Boost
, or
Automatic Energy-saving
functions.
Direct Access Number — F404
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Minimum — 0.00
Maximum — 6500.0
Units — mH
Motor Constant 4 (load inertia)
Program
Motor
Vector Motor Model
This parameter is used to control the load inertia during speed changes.
Acceleration and deceleration overshoot may be reduced by increasing this
value.
This setting (motor tuning) is required to use the
Vector Control
,
Automatic
Torque Boost
, or
Automatic Energy-saving
functions.
Direct Access Number — F405
Parameter Type —
Numerical
Factory Default —
1.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 100.0
Motor Constant 5 (leakage inductance)
Program
Motor
Vector Motor Model
This parameter provides slight increases in the output voltage of the drive at the
high speed range.
This setting (motor tuning) is required to use the
Vector Control
,
Automatic
Torque Boost
, or
Automatic Energy-saving
functions.
Direct Access Number — F410
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Minimum — 0.00
Maximum — 650.0
Number of Motor Poles
Program
Motor
Vector Motor Model
This parameter identifies the number of motor poles.
Settings:
2 — 2 Pole Motor
4 — 4 Pole Motor
6 — 6 Pole Motor
8 — 8 Pole Motor
10 — 10 Pole Motor
12 — 12 Pole Motor
14 — 14 Pole Motor
16 — 16 Pole Motor
Direct Access Number — F411
Parameter Type —
Selection List
Factory Default —
Selection 4
Changeable During Run —
No
Minimum — 2
Maximum — 16
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......