GX9 ASD Installation and Operation Manual
Input Terminal 4 (RES) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the
RES
terminal input by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F143
Parameter Type —
Numerical
Factory Default —
8
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
Input Terminal 5 – 8 (S1 – S4) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the
5 – 8
terminal inputs by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F144
Parameter Type —
Numerical
Factory Default —
8
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
Input Terminal 9 – 16 (S5 – S12) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the
9 – 16
terminal inputs by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F145
Parameter Type —
Numerical
Factory Default —
8
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
OUT1 On Delay
Program
Terminal
Output Terminal Delays
Once the condition is met to close the
OUT1
(
A
&
C
) output terminals, this
parameter delays the closing of the terminals by the programmed value.
For example, if
the
OUT1
function is programmed as
Overtorque Alarm
,
OUT1
will close 2.0 mS (the default value for
OUT1 On Delay
) after the
overtorque condition occurs.
The delay may be increased to prevent relay chatter.
Direct Access Number — F150
Parameter Type —
Numerical
Factory Default —
2
Changeable During Run —
No
Minimum — 2
Maximum — 200
Units — mS
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......