Condenser Fan and Sensor Harness Installation
IMPORTANT: Before making any electrical connections, confirm the battery cables in the TriPac Envidia battery
box and truck battery box are not connected to the batteries.
NOTE: Excessive harnesses lengths should be doubled up and secured with band wraps. DO NOT CUT THE WIRE
HARNESSES!
NOTE: Always check the male pins for straightness before attempting to mate connectors. If any resistance is felt
when mating the connector: recheck the male pin alignment. Exercise care when mating the connections to
Connector Panel.
Evaporator/Control Box
1.
Locate the Condenser Fan and Sensor harness supplied loose in the installation kit.
2.
Locate the Connector Panel located outside the Evaporator/Control Box.
3.
Connect the 6-pin connector to the Condenser (J6) connector.
4.
Route the harness down through the 2” access hole in the tractor floor and out to the condenser fan.
Condenser Assembly
5.
Connect the
4-pin
connector to the matting connector from the condenser fan.
6.
Attach the Ambient Air Sensor to the
inside
of the receiver drier bracket with the supplied clamp and
mounting hardware.
NOTE: Always install the sensor to the inside of the drier bracket for best temperature readings and to protect it
from damage.
7.
Secure all harness adequately with insulated clamps or band wraps
.
Figure 24: Condenser and Sensor Harness Connections
Summary of Contents for TriPac Envidia
Page 2: ......
Page 11: ...9 Battery Box Dimensions Figure 1 Battery Box Dimensions...
Page 12: ...10 Battery Box Dimensions continued Figure 2 Battery Box Dimensions continued...
Page 13: ...11 Evaporator Control Box Dimensions Figure 3 Evaporator Control Box Dimensions...
Page 14: ...12 Condenser with Receiver Drier Dimensions Figure 4 Condenser with Receiver Drier Dimensions...
Page 15: ...13 HMI Dimensions Figure 5 HMI Dimensions...
Page 16: ...14 1000 Watt Power Inverter Dimensions Option Figure 6 1000 Watt Power Inverter Dimensions...
Page 18: ...16 D2 D4 Heater Dimensions Option Figure 8 Heater Dimension...
Page 19: ...17 BLANK PAGE...
Page 21: ...19 Typical Component Locations Figure 9 Typical Component Locations...
Page 45: ...43 A C Duct Installation continued FLUSH MOUNTED EVAPORATOR Figure 21 A C Duct locations...
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......