Operating Instructions
50
The GAUGES and SENSORS functions are always available
from the Maintenance Menu.
In the example shown in Figure 27, the soft key functions from
the Standard Display have been changed to PRETRIP and SOT
(Start of Trip marker). The GAUGES and SENSORS
functions are always available from the Maintenance Menu.
Figure 27: PRETRIP and SOT
Display Heater
The HMI Control Panel is equipped with a display heater. This
heater is needed to make the display visible in very cold
ambient temperatures.
The HMI has its own internal temperature sensor for the
display heater. The heater is energized when the unit is turned
on and the ambient temperature is below 29.4 F (-2 C). The
heater turns off when the temperature sensed by the internal
sensor rises above 37.4 F (+3 C). The heater draws from 1.4 to
1.7 amps when energized.
The colder the ambient temperature the longer it will take for
the heater to make the display visible on a cold startup. It may
take 10-15 seconds for the display to appear with extremely
cold temperatures.
If a Language is Enabled
If more than one language has been enabled from the Guarded
Access Language Menu, a prompt will appear to allow the
desired language to be chosen as shown below. Only
ON
OFF
MENU
35
°F
35
SET
SOT
PRETRIP
POINT
.8
Summary of Contents for Precedent S-600
Page 9: ...6 ...
Page 11: ...Introduction 8 ...
Page 15: ...EPA Emission Control System Warranty Statement 12 ...
Page 38: ...Unit Description 35 Figure 13 SR 4 Controller ...
Page 39: ...Unit Description 36 ...
Page 43: ...Remote Status Display Optional 40 ...
Page 127: ...Operating Instructions 124 ...
Page 143: ...Optional Rear Remote Control Panel 140 ...
Page 179: ...Alarm Codes 176 ...
Page 197: ...Warranty 194 ...
Page 209: ...Maintenance Inspection Schedule 206 ...
Page 213: ...Serial Number Locations 210 ...
Page 217: ...214 ...