Proline Promass F 500 EtherNet/IP
Commissioning
149
Parameter
Prerequisite
Description
Selection / User
interface / User
entry
Factory setting
Assign limit
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Limit
option is selected
in the
Switch output
function
parameter.
Select process variable for limit
function.
• Mass flow
• Volume flow
• Corrected volume
flow
• Target mass flow
• Carrier mass flow
• Target volume
flow
• Carrier volume
flow
• Target corrected
volume flow
• Carrier corrected
volume flow
• Density
• Reference density
• Reference density
alternative
• GSV flow
• GSV flow
alternative
• NSV flow
• NSV flow
alternative
• S&W volume flow
• Water cut
• Oil density
• Water density
• Oil mass flow
• Water mass flow
• Oil volume flow
• Water volume flow
• Oil corrected
volume flow
• Water corrected
volume flow
• Concentration
• Temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Oscillation
damping
• Pressure
Mass flow
Assign flow direction check
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Flow direction check
option is selected in the
Switch output function
parameter.
Select process variable for flow
direction monitoring.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
Mass flow
Assign status
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Status
option is
selected in the
Switch
output function
parameter.
Select device status for switch
output.
• Partially filled pipe
detection
• Low flow cut off
Partially filled pipe
detection