Proline Promass F 500 EtherNet/IP
Commissioning
191
Parameter
Prerequisite
Description
Selection / User
entry / User
interface
Factory setting
Status input simulation
–
Switch simulation of the status
input on and off.
• Off
• On
Off
Input signal level
In the
Status input simulation
parameter, the
On
option is
selected.
Select the signal level for the
simulation of the status input.
• High
• Low
High
Current input 1 to n simulation
–
Switch simulation of the
current input on and off.
• Off
• On
Off
Value current input 1 to n
In the
Current input 1 to n
simulation
parameter, the
On
option is selected.
Enter the current value for
simulation.
0 to 22.5 mA
0 mA
Current output 1 to n simulation
–
Switch the simulation of the
current output on and off.
• Off
• On
Off
Value current output 1 to n
In the
Current output 1 to n
simulation
parameter, the
On
option is selected.
Enter the current value for
simulation.
3.59 to 22.5 mA
3.59 mA
Frequency output simulation 1 to n
In the
Operating mode
parameter, the
Frequency
option is selected.
Switch the simulation of the
frequency output on and off.
• Off
• On
Off
Frequency value 1 to n
In the
Frequency output
simulation 1 to n
parameter,
the
On
option is selected.
Enter the frequency value for
the simulation.
0.0 to 12
500.0 Hz
0.0 Hz
Pulse output simulation 1 to n
In the
Operating mode
parameter, the
Pulse
option is
selected.
Set and switch off the pulse
output simulation.
For
Fixed value
option:
Pulse width
parameter
(→ 141) defines the
pulse width of the pulses
output.
• Off
• Fixed value
• Down-counting
value
Off
Pulse value 1 to n
In the
Pulse output
simulation 1 to n
parameter,
the
Down-counting value
option is selected.
Enter the number of pulses for
simulation.
0 to 65
535
0
Switch output simulation 1 to n
In the
Operating mode
parameter, the
Switch
option
is selected.
Switch the simulation of the
switch output on and off.
• Off
• On
Off
Switch status 1 to n
–
Select the status of the status
output for the simulation.
• Open
• Closed
Open
Relay output 1 to n simulation
–
Switch simulation of the relay
output on and off.
• Off
• On
Off
Switch status 1 to n
The
On
option is selected in
the
Switch output simulation
1 to n
parameter parameter.
Select status of the relay
output for the simulation.
• Open
• Closed
Open
Pulse output simulation
–
Set and switch off the pulse
output simulation.
For
Fixed value
option:
Pulse width
parameter
defines the pulse width
of the pulses output.
• Off
• Fixed value
• Down-counting
value
Off
Pulse value
In the
Pulse output
simulation
parameter, the
Down-counting value
option
is selected.
Set and switch off the pulse
output simulation.
0 to 65
535
0