Diagnostics and troubleshooting
Proline Promass F 500 EtherNet/IP
218
Diagnostic behavior
Symbol
Meaning
Alarm
• Measurement is interrupted.
• Signal outputs and totalizers assume the defined alarm condition.
• A diagnostic message is generated.
Warning
Measurement is resumed. The signal outputs and totalizers are not affected. A diagnostic
message is generated.
Diagnostic information
The fault can be identified using the diagnostic information. The short text helps you by
providing information about the fault. In addition, the corresponding symbol for the
diagnostic behavior is displayed in front of the diagnostic information on the local display.
Diagnostic information
Diagnostic code
Diagnostic
behavior
Status signal
Diagnostic
number
Short text
↓
↓
↓
Example
A0013962
A0013958
842
Process limit
NAMUR
NE 107
3-digit number
Operating elements
Key
Meaning
Plus key
In a menu, submenu
Opens the message about remedy information.
Enter key
In a menu, submenu
Opens the operating menu.