097-55501-01 Revision M – January 2009
TimeHub 5500 User’s Guide 277
Chapter 6 Specifications
Factory Default Values
Output Driver Card Default Settings
lists the factory defaults for the TimeHub 5500 Output Driver card.
User Changes to Factory Defaults
Use
to record any changes you make to the factory default settings.
Table 6-3 DS1 and E1 Output Module Default Settings
Setting
Factory Default
Range
Enable | Disable Outputs
Enabled
Settable for each output port
Framing
N (prior to firmware
version 4236B)
Y (firmware version
4236B and higher)
Y (ESF) | N (D4)
Output Quality Level
9
1 to 9
Table 6-4 User Changes to Factory Default Settings
Setting
Factory Default
User Changes
Management Card Defaults
Security
Off
Unit Name
TimeHub
User List configurations
Maximum of 25 users
EIA-232-C Port
9600 baud
Echo = Y
Ethernet IP Address
IP Address 0.0.0.1
Gateway Address 0.0.0.1
Network Mask 255.255.248.0
Inactivity Time
100 sec
Clock Card Defaults
Bridged Mode
N
CC Delay
0 ns
Freerun Action
Continue (Master)
Squelch (Remote)
Holdover and Freerun
Quality Level
3 (ST2 Clock)
5 (ST3E Clock)