![Symmetricom TimeHub 5500 User Manual Download Page 153](http://html.mh-extra.com/html/symmetricom/timehub-5500/timehub-5500_user-manual_1419592153.webp)
097-55501-01 Revision M – January 2009
TimeHub 5500 User’s Guide 153
Chapter 4 Testing and Configuring the TimeHub
Establishing a Connection to the TimeHub
Using TL1 Commands
Use the following procedure to configure the Ethernet parameters (IP Address,
Subnet Mask, and Gateway Address).
1. Establish a direct serial connection to the TimeHub as described in
2. Use the Edit Equipment command to specify whether the automatic output
messages, and commands and responses will be carried separately on two
different ports or combined on one port.
ED-EQPT:::<ctag>:::AOMERGE=a;
where a = Y (combines automatic output messages, and commands and
responses on one port) or N (provides separate ports for automatic output
messages, and commands and responses
3. Issue the following command to copy the working memory to auxiliary memory.
CPY-MEM::NET:<ctag>::WKG,AUX;
4. Issue the following command to set the TimeHub 5500 IP address.
ED-EQPT:::<ctag>:::IPNEX=a.a.a.a;
where each a is an independent value between 0 and 255
To verify the parameter, issue the Retrieve Equipment command:
RTRV-EQPT:::<ctag>:::PARAMETER=IPNEX;
5. Issue the following command to set the subnetwork mask IP address.
ED-EQPT:::<ctag>:::IPSUBNETX=a.a.a.a;
where each a is an independent value between 0 and 255
Notes:
1.
To verify the parameter, issue the Retrieve Equipment command:
RTRV-EQPT:::<ctag>:::PARAMETER=AOMERGE;
2.
If the IP address of the manager matches ILPM1 or IPLM2, the
output will be merged, regardless of the AOMERGE value. In this
case, the local manager software is used, which does not support
having commands and events carried on separate ports. For
details on the ILPM1 and IPLM2 parameters, refer to the
TimeHub 5500 TL1 Reference Manual.