Chapter 3 Installing the TimeHub 5500
Installing Expansion Shelves
Installing Expansion Shelves
The TimeHub 5500 has two interface connectors to connect an Expansion shelf.
You can connect up to four Expansion shelves in a daisy-chain fashion using two
Expansion Interface cables (060-55591-02) per shelf. You make the connection
using the Expansion Link 1 and 2 connectors on the rear panel of the Main shelf.
Installing the Shelf in the Rack
Install the Expansion shelf using the procedure described in
Making Ground and Power Connections
The Expansion shelf has redundant -48VDC power input connections labeled A and
B. Both are located in the upper-right and upper-left corners of the rear panel; the
connections are three-position terminal blocks, as shown in
. The
connections are
not
the same as on the Master shelf.
Figure 3-20. Power and Ground Connections on the Expansion Shelf
Install power and ground connections using the procedure described in
Setting the Expansion Shelf Address
You can install up to four Expansion shelves in a daisy-chain to a Master or Remote
shelf. Each Expansion shelf requires a unique address. You set the address of the
Expansion shelf using an eight-position rotary switch on the backplane (
). This switch is located near the bottom at the left side, behind the slot for
Expansion Controller card 1 (labeled EC1). The factory default setting is “1”.
Warning:
To avoid possible damage to the shelf and to the office
power supply, connect power wiring as indicated on the rear of the
Expansion shelf. The power connections on the Expansion shelf are
not
the same as on the Master shelf.
A. TB1 Connections
(Office Battery A)
B. TB2 Connections
(Office Battery B)