Chapter 4 Testing and Configuring the TimeHub
Installing Cards into the Front Panel
Installing the Management Card
To install the Management card, perform the following steps:
1. Visually inspect the Master/Remote switch S1 on the shelf to verify that it is in
for the appropriate setting.
2. Ensure that switch S1 on the Management card is set to the default Off position
(see
). This allows you to set up the TimeHub without
having to create a user and password.
3. Insert the Management card into the MC slot (the leftmost slot in the shelf).
Ensure that the card aligns properly with its mating backplane connector, then
push the card into place until it is fully seated into the backplane connectors. Do
not tighten the captive screws at this time.
The Power LED turns on and the Alarm LED stays lit until the self-test finishes;
the ALARMS Shelf Critical LEDs remains lit since there is no Clock card installed.
4. Verify that the alarm relays are operating correctly using an ohmmeter. The relay
pins are on the Input/Alarm Connector module on the rear panel of the shelf.
Measure between the Critical Common pin and the NO pin, and again between
the Critical Common pin and the NC pin. The Common-to-NO readings should
be shorted and the Common-to-NO readings should be open. Repeat for the
Major relay pins.
5. Remove the (A) fuse from the front panel of the shelf by pressing and twisting
the holder in a counterclockwise direction with a blade screwdriver. The SHELF
POWER –48V A Fail and the ALARMS Shelf Critical LED is present.
6. Replace the –48 volt A fuse. The SHELF POWER –48V A Fail LED turns off,
and the ALARMS Shelf Major LED turns off within a few seconds.
7. Remove the (B) fuse by twisting in a counterclockwise direction. The SHELF
POWER –48V B Fail and the ALARMS Shelf Major LEDs light.
8. Replace the (B) fuse from the front panel of the shelf. The SHELF POWER
–48V B Fail LED turns off, and the ALARMS Shelf Major LED turns off within a
few seconds.
9. Press the AUDIBLE ALARM Cutoff pushbutton on the Management card (
). The ALARMS Cutoff LED lights.
Note:
After you install the clock modules, the ALARMS Shelf Major
LEDs light. The TimeHub 5500 should be configured with at least two
clock modules, if not, a critical alarm will be present.