097-55501-01 Revision M – January 2009
TimeHub 5500 User’s Guide 115
Chapter 3 Installing the TimeHub 5500
Making Signal Connections
Figure 3-13. Rear Panel Connectors on the Main Shelf
Making Shelf–to–Panel Connections
Connect the factory-supplied cable from the connector on the Output Connector
card on the rear panel of the shelf to the appropriate connector on the wire-wrap
panel. Repeat as needed, depending on the number of outputs used. Refer to
.
Dress the cables using your company standards.
Earth Grounding of cables and systems must be a single point ground. Each Earth
Grounding Lug must not be stacked upon any other grounding lug.
Note:
The shield drain conductor is provided to ground to the rack
frame ground at the wire-wrap connector end.
If the timing lead is connected to a Network Element with an isolated
ground configuration, then terminate the shield wire at the Network
Element.
Battery A and
Frame Ground
Battery B and
Frame Ground
Local
Comm Port
Reserved for
future use
Expansion Ports
Reserved for
future use
LAN Port