097-55501-01 Revision M – January 2009
TimeHub 5500 User’s Guide 167
Chapter 4 Testing and Configuring the TimeHub
Provisioning the NTP Parameters
To retrieve the current selection, issue the command:
RTRV-EQPT::CLK:SV42:::PARAMETER=SYNCMDE;
12. Enable SSM reading for ESF-framed DS1 inputs. Inputs that are incapable of
SSM decoding (such as PRS or D4-framed DS1) use an assumed SSM value
(see keyword QLEVEL in the
TL1 Reference Manual
). The ESF-framed DS1
inputs will also use an assumed value unless reading of SSM is enabled.
To enable SSM decoding for a given ESF-framed DS1 reference, issue the
command:
ED-SYNC::CLK-a:<ctag>:::SSMENB=b;
where a = 1 – 4 and is the input reference that should decode SSM.
a = N disables decoding
For example, to enable SSM decoding on input 1 (first DS1 input), issue the
command:
ED-SYNC::CLK-1:SV48:::SSMENB=Y;
To retrieve the current setting of SSM decoding for input 1, issue the command:
RTRV-EQPT::CLK-1:SV49:::PARAMETER=SSMENB;
To continue provisioning a Master shelf, continue at
Provisioning the NTP Parameters
You must assign an IP address, mask, and gateway address for each port you are
using on the NTP Server card. Each time you change an NTP parameter, you must
issue the ED-EQPT command with the APPLYCFG keyword to apply the changes.
You can issue the command immediately before or after issuing the change
command. For further information on these commands, see the
TimeHub 5500 TL1
Reference Guide
(097-55502-01). You can also use the TimeCraft 1.3 application to
provision the NTP Server card; see the TimeCraft 1.3 manual for details.
Caution:
To avoid accidentally corrupting the NTP configuration files,
do not remove the NTP Server card from the shelf for five minutes
after installing it or after powering up the TimeHub shelf.