Appendix A
System Specifications and Site Requirements
85
■
Circuit breakers must be located between the DC power source and the StorEdge
S1 storage enclosure. You should use two 10-amp, double-pole, fast trip, DC-rated
circuit breakers for each power supply.
DC Supply and Ground Conductor Requirements
■
Copper is the only suitable conductor material
■
Power supply connections through the input connector: 12 AWG (between the
StorEdge S1 and the circuit breaker). There are three conductors:
■
-48V
■
Ground connection to the power supply
■
-48V Return
■
System ground conductor: 6 AWG (to be connected to the chassis)
■
Cable insulation rating: minimum of 75C, low smoke fume (LSF), flame retardant
■
Cable type to be one of the following:
■
UL style 1028 or other UL 1581(VW-1) compliant equivalent
■
IEEE 383 compliant
■
IEEE 1202-1991 compliant
■
Branch circuit cable insulation color: per applicable National Electrical Codes
■
Grounding cable insulation color: green/yellow
Summary of Contents for StorEdge S1 AC100
Page 8: ...viii StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 22: ...xxii StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 30: ...xxx StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 32: ...xxxii StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 52: ...16 StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 64: ...28 StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 92: ...56 StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 116: ...80 StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 128: ...Index 92 StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...