84
StorEdge S1 AC100 and DC100 Installation and Maintenance Manual • March 2002
Ensure that all methods of disconnecting the power remain accessible after
installation.
Caution –
External filtering and surge suppression devices might be required on
the power feeds where branch circuit electromagnetic characteristics are unknown.
DC Source Power Requirements
DC power must be:
■
Electrically isolated from any AC source
■
Reliably connected to earth (the battery room positive bus is connected to ground)
■
Capable of providing up to 200 watts of continuous power per feed pair
Note –
The DC version of the StorEdge S1 storage enclosure must be installed in a
restricted access location. Per the intent of the National Electrical Code, a restricted
access location is an area intended for qualified or trained personnel only and has
access controlled by some sort of locking mechanism, such as a key lock or an access
card system.
Overcurrent Protection Requirements
Note –
Overcurrent protection devices must meet applicable national and local
electrical safety codes and be approved for the intended application.
■
Overcurrent protection devices must be provided as part of each host equipment
rack.
TABLE A-3
DC Power Requirements
Electrical Element
Requirement
Voltage
-48 VDC
Input current
< 4.0 amps @ -40 VDC (150 W)
Max. input surge current
• 20 amps peak on a cold start (after AC has been off for more
than 200 ms)
• 100 amps peak on a warm start (after AC has been off for
less than 200 ms)
Summary of Contents for StorEdge S1 AC100
Page 8: ...viii StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 22: ...xxii StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 30: ...xxx StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 32: ...xxxii StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 52: ...16 StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 64: ...28 StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 92: ...56 StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 116: ...80 StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...
Page 128: ...Index 92 StorEdge S1 AC100 and DC100 Installation and Maintenance Manual March 2002...