background image

 

animeo KNX 4 DC Motor Controller 

28.02.2019 

 

WM 24 V DC 

 
 

 2019 Somfy Activités SA 

 Ref. 5147817A 

56/56 

 

Summary of Contents for Animeo 1870452

Page 1: ...animeo KNX 4 DC Motor Controller 28 02 2019 WM 24 V DC 2019 Somfy Activités SA Ref 5147817A 1 56 68 2019 SOMFY ACTIVITES SA ALL RIGHTS RESERVED REF 5147817A 2019 01 31 ...

Page 2: ...ex card General 22 6 2 Menu index card Configuration for motor 1 4 25 6 3 Menu index card Functions for motor 1 4 28 6 4 General information for Binary inputs 30 6 5 Menu index card Binary inputs Venetian blind Up Down 31 6 6 Menu index card Binary inputs Switch Dry contact 32 6 7 Menu index card Binary inputs 8 Bit value rising edge 34 6 8 Menu index card Binary inputs Dimming 35 6 9 Menu index c...

Page 3: ... all four motors independently of ETS programming Testing the moving direction of the motors is possible without ETS The device can be used in delivery state without programming with the ETS software Four local push button inputs can be used as maximum to connect eight universal KNX binary inputs for example window contacts temperature switches or presence detectors By using conventional push butt...

Page 4: ... button ergonomics With this parameter it is ensured that the Venetian blind is controlled in the EU ergonomics over the local push button inputs or over the Somfy RTS radio hand transmitter Short pressing of the push button 0 5 s A turn step is carried out Long pressing of the push button 0 5 s A turn command is carried out as long as the push button is pressed If the current position of the Vene...

Page 5: ...tion Turning direction Angle 45 Turn 50 KNX value 50 Angle 90 Turn 0 KNX value 100 Max closed 50 turned Turning direction Angle 0 Turn 100 KNX value 0 Max turned 1 7 2 90 90 Venetian blind Turning direction Turning direction Angle 0 Turn 50 KNX value 50 Angle 90 Turn 0 KNX value 100 Max closed 50 turned Turning direction Angle 90 Turn 100 KNX value 0 Max turned ...

Page 6: ...02 2019 WM 24 V DC 2019 Somfy Activités SA Ref 5147817A 6 56 2 Installation Choose the right place for installation Level surface with sufficient space Installation of the Motor Controller 4 DC WM Complete wiring and connect power supply ...

Page 7: ... US LED blinks Connecttion to Cable Twisted pair Max length Stripping length Motors Min 2 x 0 6 mm 22 AWG Max 2 x 2 5 mm2 13 AWG 6 mm 0 24 Switch Min 3 x 0 6 mm 22 AWG Max 3 x 2 5 mm2 13 AWG Recommended 100 m 330 ft 6 mm 0 24 Group control Min 3 x 0 6 mm 22 AWG Max 3 x 1 5 mm2 15 AWG Recommended 100 m 330 ft 6 mm 0 24 KNX Bus 2 x 0 8 mm 20 AWG Required according to KNX guidelines 6 mm 0 24 24 V DC...

Page 8: ...ventional push buttons is possible The local push button inputs are assigned directly to the motor outputs Push button input 1 controls motor output 1 fig 1 The motor outputs can be controlled through bridging the wire at the push button inputs when required fig 2 4 1 Function of the Reset Prog button H The basic settings in the KNX Motor Controller can be made using this push button These basic s...

Page 9: ...programmed no further settings of the user ergonomics can be made via the Reset Prog button When the device is unassigned by the ETS the adjusting of the user ergonomics is possible again via the Reset Prog button H The selection of the user ergonomics must match with a corresponding end product Learning in of animeo RTS radio module SCR Screen ergonomics EU Venetian blind EU ergonomics US Venetia...

Page 10: ...f 1860105 A setting using animeo KNX RTS Receiver ref 1860191 and Somfy RTS Transmitter resp animeo EnOcean Receiver ref 1860220 or animeo KNX EnOcean Receiver ref 1860229 und EnOcean Receiver is not possible 4 5 Manual learning in of the intermediate position 1 Intermediate position 1 can be learned in individually per motor output via conventional local push buttons At the same time it is possib...

Page 11: ...via the Reset Prog push button can be set back to the delivery state by pressing the Reset Prog button for 10 seconds When the device has been programmed with the ETS software When the device has been programmed with the ETS software a reset in the delivery state is no longer pos sible via the Rest Prog button Over the function Unload in the ETS all settings of the device can be set back in the de...

Page 12: ...h the value 1 and UP with the receiving of a telegram with the value 0 The duration of the turning step is defined in the parameter settings With vertical awnings roller shutters awnings and windows When one of the end products is moving the move is stopped with the receiving of a telegram on one of these communication ob jects no matter whether 0 or 1 is received If one of these end products is n...

Page 13: ... 1 4 move to the ETS parameterized per local switch or to the radio transmitted learned in intermediate position 1 if the learned in position is valid With the re ceiving of a telegram with the value 0 on this communication object the blinds 1 4 move to the upper end position 30 Motor 1 Move to IP2 1 bit 1 008 If a telegram with the value 1 is received on one of these communication objects the cor...

Page 14: ...com mands will be accepted again If Repeat last tel egram after security Yes has been selected in the ETS parameters the blinds move to the posi tion they have been before security was acti vated If on the communication object 49 Security high prio a telegram is received with the value 1 the blinds 1 4 move to the position parameterized in the ETS Security high prio 45 Motor 1 Security high prio 1...

Page 15: ...it 1 001 If a telegram with the value 1 is received on this communication object the functions parameter ized in the ETS for the blinds 1 4 are blocked If a telegram with the value 0 is received on this communication object the functions parameter ized in the ETS for the blinds 1 4 are no longer blocked and freed again 56 Motor 1 Prio automatic manual 1 bit 1 003 Over these communication objects t...

Page 16: ...gh these communication objects a telegram with the value 1 for the corresponding blind is sent when the upper end position is reached When leaving the upper end position of the corre sponding blind a telegram with the value 0 is sent The upper and lower end position is deter mined by the parameterized move times 82 Motor 2 Upper end position 1 bit 1 002 83 Motor 3 Upper end position 1 bit 1 002 84...

Page 17: ...ommunication object with the value 1 or 0 100 Switch input 1 A 8 Bit value 1 Byte 5 010 According to the parameter settings with a rising edge on input 1 contact A the parameterized value 0 255 is sent 101 Switch input 1 B 8 Bit value 1 Byte 5 010 According to the parameter settings with a rising edge on input 1 contact B the parameterized value 0 255 is sent 102 Switch input 1 A B Dimming 1 Bit 1...

Page 18: ...ct 103 E F instead of A B 120 Switch Input 4 UP DOWN 1 Bit 1 008 see description of object 96 G H instead of A B 121 Switch Input 4 STEP STOP 1 Bit 1 008 see description of object 97 G H instead of A B 122 Switch Input 4 G Switch 1 Bit 1 001 see description of object 98 G instead of A 123 Switch Input 4 H Switch 1 Bit 1 001 see description of object 99 H instead of B 124 Switch Input 4 G 8 Bit val...

Page 19: ... Dimming ON OFF or Slow Tilting UP DOWN 1 Bit 1 001 On Up According to the parameter settings a short pressing of UP button at channel 1 learned in remote a telegram with the value 0 will be gen erated The light will be switched ON or the blinds will move UP Off Down According to the parameter settings a short pressing of DOWN button at channel 1 learned in remote a telegram with the value 1 will ...

Page 20: ...bject 130 channel 3 instead of channel 1 151 Radio Input 3 8 Bit value my but ton 1 Byte 5 010 see description of object 131 channel 3 instead of channel 1 152 Radio Input 3 Switch UP button 1 Bit 1 001 see description of object 132 channel 3 instead of channel 1 153 Radio Input 3 Switch DOWN but ton 1 Bit 1 001 see description of object 133 channel 3 instead of channel 1 154 Radio Input 3 8 Bit v...

Page 21: ...bject 130 channel 5 instead of channel 1 171 Radio Input 5 8 Bit value my but ton 1 Byte 5 010 see description of object 131 channel 5 instead of channel 1 172 Radio Input 5 Switch UP button 1 Bit 1 001 see description of object 132 channel 5 instead of channel 1 173 Radio Input 5 Switch DOWN but ton 1 Bit 1 001 see description of object 133 channel 5 instead of channel 1 174 Radio Input 5 8 Bit v...

Page 22: ... Selection options Combined Individual With these parameters the settings of the motor outputs are made as to whether Combined or Individual With the parameter Combined only one menu index card becomes visible for the basic settings of all four motor outputs motor 1 4 H The selection Combined is recommended for projects for which the settings of the motor outputs are the same With the parameter In...

Page 23: ...ith the next automatic command H See chapter 1 Definitions Priority manual function When a manual command 1 bit occurs before an automatic command 1 byte all automatic commands are disabled A manual command is also generated over the local push button inputs or via the radio trans mitter A reset of the priority manual function occurs when Priority reset 60 63 receives 1 or 0 on the corresponding o...

Page 24: ...s parameter it is determined whether the input is blocked to the group control or is freed Over this input all four motors are selected at the same time Regardless of the parameter settings the security set tings objects 40 49 have higher priority If one of the security objects is active the input to the group control is blocked H With a bus power failure this input is freed Even if it is blocked ...

Page 25: ...h button inputs or via the Somfy RTS radio transmitter When the local push button inputs are used as universal push button inputs the operating ergonomics are defined over the corresponding parameters short long pressing of the push button The operating ergonom ics using a Somfy RTS radio transmitter remains unchanged H For an explanation of EU US ergonomics and screen ergonomics see chapter 1 Def...

Page 26: ...g time from the lower end position to the upper end posi tion or the maximum running time which a window motor needs to close the corresponding window An ex cess time of 5 seconds is always added except with position telegrams objects 13 16 If a position tele gram with the value 0 is sent to the corresponding object an excess time of 5 seconds is still added to it 6 2 3 Running time Down Open Defa...

Page 27: ...Functions motor 1 4 the blind moves after ending of the Low priority value 0 again in the last position and angle before activation of this priority 6 2 8 Security position High priority Default value Upper end limit Selection options Upper end limit Lower end limit Ignore security Stop Close window Open window The Security position high priority for the corresponding blind is determined with this...

Page 28: ...meter the intermediate position 1 UP DOWN is defined The set value in refers to the parameterized move times of the corresponding blind of the menu index card Motor 1 4 Motor 1 4 If the IP UP Down position parameter is set to 0 the IP position is disabled This function avoids any movement of the blinds by using the my or IP push button 6 3 1 2 Slat position 0 100 Default value 0 Selection options ...

Page 29: ...s parameter If a telegram with the value 1 is received on the corresponding object during a blinds move this move is carried out up to the end Only then are further move commands byte blocked If a telegram with the value 0 is received on the corre sponding object the move commands byte are released again 6 3 4 Block slat orders 1 Byte Default value No Selection options No Yes Slat orders byte can ...

Page 30: ...als are freed again H This function is deactivated for local push button inputs if Yes has been selected in the Use universal binary inputs menu index card see section 6 1 4 6 3 8 Repeat last telegram after security Default value No Selection options No Yes If this parameter is set to Yes the last move command is repeated after security This means that it will move to the position which was active...

Page 31: ...n 0 5 seconds With a shorter activation which is smaller than 0 5 seconds a short term telegram is generated 6 5 3 Contact type input A Default value Normally open Selection options Normally open Normally closed Over this parameter it is defined which type of contact is at the local input A Normally open The contact at the local input is activated closed and not activated opened Normally closed Th...

Page 32: ... a rising edge at the local input appears the object value On is generated If a falling edge at the local in put appears the object value Off is generated The duration of the activation is not evaluated Rising Off falling On If a rising flank at the local input appears the object value Off is generated If a falling flank at the local in put appears the object value On is generated The duration of ...

Page 33: ...d The duration of the activity is not evaluated No evaluation If a rising or falling flank at the local input appears this is not evaluated 6 6 3 Edge evaluation contact B For detailed information see Edge evaluation contact A 6 6 4 Send starting value on Bus power return Default value No Selection options Yes No If this parameter is stopped the current state of the input is transmitted with the b...

Page 34: ...pervision time of the receiver is approximately 4 times higher than that of the transmitter 6 7 Menu index card Binary inputs 8 Bit value rising edge 6 7 1 Basic Function Selected option 8 Bit value rising edge 6 7 2 Contact type input A Default value 0 Selection options 0 255 With this parameter the value is set which is transmitted with a rising edge to the local input A 6 7 3 Contact A value on...

Page 35: ... input is activated opened and not activated closed 6 8 Menu index card Binary inputs Dimming 6 8 1 Basic Function Selected option Dimming 6 8 2 Long operation dimming after Default value 0 5 seconds Selection options 0 3 5 0 seconds This parameter defines the activity time of the corresponding push button which makes a distinction between the sending of a switching telegram and a dimming telegram...

Page 36: ...activated closed 6 8 6 Dimming with Default value Stop telegram Selection options Cyclic intervals Stop telegram Cyclic intervals With a short pressing of the push button at the local input A or B an On or an Off telegram is generated over the corresponding object 1 bit With a long pressing of the push button at the local input A brighter dimming is done over the corresponding object 4 bit as long...

Page 37: ...sing H When Dimming with cyclic intervals is parameterized attention must be paid to the fact that the dimming length of steps and the interval for the cyclical dimming are matched to the dimming time of the actuator 6 8 8 Interval for cyclic dimming Default value 0 5 seconds Selection options 0 5 7 0 seconds This parameter defines the duration of an interval for cyclical sending If for example a ...

Page 38: ...ge return until the first telegram can be transmitted 6 9 2 Limit number of telegrams Default value No Selection options Yes No This parameter opens the parameter to set the telegram rate limitation In addition the number of the tele grams which are transmitted cyclically per time unit can be limited 6 9 3 Limit Default value 127 telegrams per 17 sec Selection options 30 telegrams per 17 sec 60 te...

Page 39: ...s menu index card a start up delay can be set for every single motor output 6 10 1 Start delay Motor 1 4 Default value 0 seconds Selection options 0 seconds 0 100 seconds If electronic motors are controlled using this Motor Controller it is imperative to set the start delay time of the electronic motor in the settings of the Motor Controller ...

Page 40: ...ault value Ignore Selection options Upper end limit Lower end limit Ignore Intermediate position 1 IP 1 Intermediate position 2 IP 2 Close window Open window This parameter defines the position which is moved to with a bus power failure 6 11 1 2 Reaction at bus power failure Default value Ignore Selection options Upper end limit Lower end limit Ignore Intermediate position 1 IP 1 Intermediate posi...

Page 41: ...n which is moved to with a mains power return 24 V 6 11 3 Automatic cascading Default value No Selection options No Yes If this parameter is set on Yes the motor outputs with one second delay in each case move to the corre sponding position This delay time is taken into account with the start up of the positions which are gener ated from the settings Reaction with bus voltage return and Reaction w...

Page 42: ...arameter Type of feedback Upper Lower end positions 6 12 2 Type of feedback Upper Lower end positions Default value Combined if all are Up Down Selection options Combined if all are Up Down Individual Combined if all are Up Down If this parameter is selected the corresponding upper or lower end position is only announced on the bus when all four blinds have reached the upper object 85 or the lower...

Page 43: ...55 lower 0 255 slats opened 255 0 slats closed The value for the position of the slats which is transmitted over the cor responding object is dependent on the parameter settings on the menu index card General Slats turn Closed Turned ONLY WITH VENETIAN BLIND None No positions on the bus are messaged 6 12 4 Motor 1 4 Type of feedback Default value On demand Selection options On demand Status change...

Page 44: ...r radio input For every radio input there are five different basic functions for selection Default value Venetian blind Up Down Selection options Venetian blind Up Down Switch 8 Bit value rising edge Dimming Venetian blind slow tilting The single functions and parameters which arise depending on the selection of the basic functions are now described To illustrate this another basis function has be...

Page 45: ...short term telegram Step Stop and a long term telegram Up Down If the time for example is parameterized on 0 5 seconds then only after a pressing of more than 0 5 seconds is a long term telegram generated With a pressing of the push button which is shorter than 0 5 seconds a short term telegram is generated 6 15 3 Functionality of my push button Default value No function Selection options 1 Bit va...

Page 46: ...uration of the activity is not evaluated No function If the my button in the radio transmitter is pressed no object is generated H See chapter 1 Definitions for On 1 Off 0 Toggle 1 0 6 15 3 2 8 Bit value Default value 0 Selection options 0 0 255 With this parameter the value 0 255 is set which is transmitted while pressing the my button in the radio transmitter 6 15 3 3 No function If the my butto...

Page 47: ...pressed no object is generated H See chapter 1 Definitions for On 1 Off 0 Toggle 1 0 6 16 3 Functionality of the Down push button Default value Off Selection options On Off Toggle No function On If the Down button in the radio transmitter is pressed the object value On is generated The duration of the activity is not evaluated Off If the Down button in the radio transmitter is pressed the object v...

Page 48: ... duration of the activity is not evaluated Toggle If the my button in the radio transmitter is pressed the object value toggles between On and Off The duration of the activity is not evaluated No function If the my button in the radio transmitter is pressed no object is generated H See chapter 1 Definitions for On 1 Off 0 Toggle 1 0 6 16 4 2 8 Bit value Default value 0 Selection options 0 255 With...

Page 49: ...meter the value 0 255 is set which is transmitted while pressing the my button in the radio transmitter 6 17 3 Value of the Down push button Default value 0 Selection options 0 255 With this parameter the value is set which is transmitted while pressing the Down button in the radio trans mitter 6 17 4 Functionality of my push button Default value No function Selection options 1 Bit value 8 Bit val...

Page 50: ...d Toggle If the my button in the radio transmitter is pressed the object value toggles between On and Off The duration of the activity is not evaluated No function If the my button in the radio transmitter is pressed no object is generated H See chapter 1 Definitions for On 1 Off 0 Toggle 1 0 6 17 4 2 8 Bit value Default value 0 Selection options 0 255 With this parameter the value 0 255 is set wh...

Page 51: ...a short term telegram On Off and a long term telegram Brighter darker dimming If the time for example is set at 0 5 seconds a long term telegram is generated after a longer pressing than 0 5 seconds With a pressing duration which is shorter than 0 5 seconds a short term telegram is generated 6 18 3 Dimming Brighter Darker Default value Adjust by Selection options Adjust by 100 1 16 This parameter ...

Page 52: ... duration of the activity is not evaluated Toggle If the my button in the radio transmitter is pressed the object value toggles between On and Off The duration of the activity is not evaluated No function If the my button in the radio transmitter is pressed no object is generated H See chapter 1 Definitions for On 1 Off 0 Toggle 1 0 6 18 4 2 8 Bit value Default value 0 Selection options 0 255 With...

Page 53: ... Up Down and a long term telegram Open Close If the time for example is set at 0 5 seconds a longterm telegram is generated after a longer pressing than 0 5 seconds With a pressing duration which is shorter than 0 5 seconds a shortterm telegram is generated 6 19 3 Tilt slats slowly Open Close This parameter defines the turn of the Venetian blinds which is transmitted as a telegram with a long pres...

Page 54: ...d Toggle If the my button in the radio transmitter is pressed the object value toggles between On and Off The duration of the activity is not evaluated No function If the my button in the radio transmitter is pressed no object is generated H See chapter 1 Definitions for On 1 Off 0 Toggle 1 0 6 19 4 2 8 Bit value Default value 0 Selection options 0 255 With this parameter the value 0 255 is set wh...

Page 55: ...ELV Rated current consumption KNX As per KNX guidelines 10mA Max motor current consumption 4 x 2 3 A 24 V DC Supply voltage of group control input SELV 16 V DC Supply voltage of local push buttons SELV 16 V DC Terminals Spring connectors Relay micro gap Terminal KNX KNX bus terminal black red Running time per output Max 5 minutes Operating temperature 5 C to 45 C Relative humidity max 85 Material ...

Page 56: ...animeo KNX 4 DC Motor Controller 28 02 2019 WM 24 V DC 2019 Somfy Activités SA Ref 5147817A 56 56 ...

Reviews: