![SOMFY Animeo 1870452 Manual Download Page 13](http://html.mh-extra.com/html/somfy/animeo-1870452/animeo-1870452_manual_1317508013.webp)
animeo KNX 4 DC Motor Controller
28.02.2019
WM 24 V DC
2019 Somfy Activités SA
Ref. 5147817A
13/56
No. Object name
Type
DPT_ID Description
20
Motor 4 Slat position
1 Byte 5.001
is moving and receives a value on the corre-
sponding object, the position of the slats is
moved to only when the move has been com-
pleted. Depending on the parameter settings on
the card index
“General” the position is defined
as follows:
”100” = slats max. closed/
”0” = slats max. turned
or
”0” = slats max. closed/
”100” = slats max. turned
value (0/100)
value (100/0)
25
Motor 1 Move to IP1
1 bit
1.008
If a telegram with the value
“1” is received on one
of these communication objects, the correspond-
ing blind moves to the ETS parameterized per
local switch or to the radio transmitted, learned-in
intermediate position 1, if the learned-in position
is valid. With the receiving of a telegram with the
value
“0” on one of these communication objects,
the corresponding blind moves to the upper end
position.
26
Motor 2 Move to IP1
1 bit
1.008
27
Motor 3 Move to IP1
1 bit
1.008
28
Motor 4 Move to IP1
1 bit
1.008
29
Motor 1-4 Move to IP1
1 bit
1.008
If a telegram with the value
“1” is received on this
communication object, the blinds 1-4 move to the
ETS parameterized per local switch or to the
radio transmitted, learned-in intermediate position
1, if the learned-in position is valid. With the re-
ceiving of a telegram with the value
“0” on this
communication object, the blinds 1-4 move to the
upper end position.
30
Motor 1 Move to IP2
1 bit
1.008
If a telegram with the value
“1” is received on one
of these communication objects, the correspond-
ing blind moves to the intermediate position 2 pa-
rameterized in the ETS parameters. With the re-
ceiving of a telegram with the value
“0” on one of
these communication objects, the corresponding
blind moves to the upper end position.
31
Motor 2 Move to IP2
1 bit
1.008
32
Motor 3 Move to IP2
1 bit
1.008
33
Motor 4 Move to IP2
1 bit
1.008
34
Motor 1-4 Move to IP2
1 bit
1.008
If a telegram with the value
“1” is received on this
communication object, the blinds move to the
Intermediate Position (IP) 2 parameterized in the
ETS parameters. With the receiving of a telegram
with the value
“0” on this communication object
the blinds 1-4 move to the upper end position.
40
Motor 1 Security, low prio
1 bit
1.001
If a telegram with the value
“1” is received on one
of these communication objects, the correspond-
ing blind moves to the position parameterized in
the ETS parameters (Security, low prio) and any
41
Motor 2 Security, low prio
1 bit
1.001
42
Motor 3 Security, low prio
1 bit
1.001