Rising Off
If a rising flank at the local input appears, the object value “Off” is generated. If a falling flank at the local in-
put appears, this is not evaluated. The duration of the activity is not evaluated.
•
Falling Off
If a falling flank at the local input appears, the object value “Off” is generated. If a rising flank at the local in-
put appears, this is not evaluated. The duration of the activity is not evaluated.
•
Rising toggle
If a rising flank at the local input appears, the object value is inverted. If a falling flank at the local input
appears, this is not evaluated. The duration of the activity is not evaluated.
•
Falling toggle
If a falling flank at the local input appears, the object value is inverted. If a rising flank at the local input
appears, this is not evaluated. The duration of the activity is not evaluated.
•
Rising toggle, falling toggle
If a rising or falling flank at the local input appears, the object value is inverted. The duration of the activity is
not evaluated.
•
No evaluation
If a rising or falling flank at the local input appears, this is not evaluated.
6.6.3 Edge evaluation contact B
For detailed information see Edge evaluation contact A.
6.6.4 Send starting value on Bus power return
Default value:
No
Selection options:
Yes
No
If this parameter is stopped, the current state of the input is transmitted with the bus voltage return. If this
parameter is set to “No”, the current state of the input is not transmitted.
6.6.5 Contact A and B Cyclic sending of status
Default value:
No cyclic sending
Selection options:
No cyclic sending
On
Off
On and Off
With this parameter it is defined whether the corresponding switch value of the communication object should
be transmitted cyclically.
•
No cyclic sending
The switching value of the communication object is not transmitted cyclically.
•
On
If the object value is “1”, this is transmitted cyclically. If the object value changes by flank change at the local
input or reception of a telegram on “0”, the cyclic sending stops.
•
Off
If the object value is “0”, this is transmitted cyclically. If the object value changes by flank change at the local