![SOMFY Animeo 1870452 Manual Download Page 42](http://html.mh-extra.com/html/somfy/animeo-1870452/animeo-1870452_manual_1317508042.webp)
animeo KNX 4 DC Motor Controller
28.02.2019
WM 24 V DC
2019 Somfy Activités SA
Ref. 5147817A
42/56
value (0%)
value (100%)
6.12 Menu i
ndex card “Feedback motor position”
On this menu index card the parameters can be selected to announce the position status of the individual
blinds on the bus. In addition, the generated status positions are based on the parameterized move times
and turn times of the menu index cards motor
1…4 or motor 1 - 4.
6.12.1 Feedback of status Upper/Lower end positions
Default value:
No
Selection options:
No
Yes
This parameter opens the parameter “Type of feedback Upper/Lower end positions”.
6.12.2 Type of feedback Upper/Lower end positions
Default value:
Combined if all are Up/Down
Selection options:
Combined if all are Up/Down
Individual
•
Combined if all are Up/Down
If this parameter is selected, the corresponding upper or lower end position is only announced on the bus,
when all four blinds have reached the upper (object 85) or the lower (object 95) end position.
•
Individual
If this parameter is selected, the corresponding upper or lower end position is announced on the bus for each
blind individually. Here, the objects in each case (81-84) and (91-94) are made available.
6.12.3
Motor 1…4 Feedback
Default value:
None
Selection options:
Up/Down position
Slat position
Up/Down and slat position
None